AFL's Dossert® line of connectors have been used underground almost since the first underground electrical distribution systems were installed. Early records show that Dossert connectors were used in underground installations dating from 1910.
52a8df1c09764d8682f3d27d16f0da42
Product Catalog MICON Accessories, Connectors, Limiter Assemblies NETWORK UNDERGROUND
Founded in 1984, AFL is an international manufacturer providing end-to-end solutions to the energy, service provider, enterprise, hyperscale and industrial markets. AFL’s products are in use in over 130 countries and include fiber optic cable and hardware, transmission and substation accessories, outside plant equipment, connectivity, test and inspection equipment, fusion splicers and training. AFL also offers a wide variety of services supporting data center, enterprise, wireless and outside plant applications. AFL is dedicated to bringing our customers a quality product as well as delivering superior value. COMPANY WITH QUALITY SYSTEM CERTIFIED BY DNV GL ISO 9001
1 AFLglobal.com 1 (800) 890-8878 11.23.2026 1 Network Underground Table of Contents Alphanumeric Connector Type Index 2 Pictorial Index 3 Introduction 5 TECH: MICON 6 TECH: MICON Insulation 7 TECH: MICON Ordering Data 9 Limiter Fusing Characteristics 10 MICON Coupling Type MIC 11 Type MA Cable Receptacle 12 MICON Outlet Plugs Type P 13 Type C Tapered Compression Sleeve 14 Type CKS Compression Receptacle 15 Type MIS Insulating Sleeve 16 Type STC Cable Coupler 17 Types NRLA-R123, NRLA-P123 Limiter Link Assembly 18 Type NRLA-PL123 Long Limiter Link Assembly 19 Types NRLA-R3, NLRA-P3 Limiter Link 20 Type NRLA-PL3 Long Limiter Link 21 Types NRLA-R2, NRLA-P2 Limiter Shell for NRLA-R3, NRLA-P3, NRLA-PL3 22 Type NRLA-1 Insulating Sleeve for NRLA-P, NRLA-R, NRLA-PL 23 Types LLA-2R123, LLA-2P123 Limiter Terminal Assembly 24 Type LLA-2PL123 Long Limiter Terminal Assembly 25 Types LLA-2R3, LLA-2P3 Limiter Terminal 26 Type LLA-2PL3 Long Limiter Terminal 27 Type LLA-2P2 Limiter Terminal Shell 28 Type LLA-2P1 Limiter Terminal Insulating Sleeve 29 Types ML-R123, ML-P123 MICON Limiter Assembly 30 Type ML-PL123 MICON Long Limiter Assembly 31 Types ML-R3, ML-P3 MICON Limiter 32 Type ML-PL3 MICON Long Limiter for Paper Insulated Cable 33 Types ML-R2, ML-P2 Limiter Shell 34 Type ML-1 MICON Limiter Insulating Sleeve 35 Types BCLA-R123, BCLA-P123, BCLA-PL123 Limiter Tap Assembly 36 Type RLB-E Renewable MICON Limiter Link Assembly 37 Type RLM-B Limiter Mounting Block 38 Type RL-2 Compression Terminal 39 Type RLM-E Renewable Limiter Link Assembly 40 Type RLL-E Renewable Limiter Link Coupler 41 Type RLBC-E Renewable Limiter Link Connector 42 Type RLLA-E Special Renewable Link Connector 43 Type NCLA-E Straight Tap Connector 44 Types CRC and CRC-C Insulating Caps 45 Type CRW Thermal Insulating Wedge 46 Type DPC Compression Coupler 47 Type DPR Compression Reducing Coupler 48 Type CRT Compression Tee Coupler 49 Type DPL Compression Terminal Lug 51 Type BCKT Tee Connector 53 Type HNT Hood Nut Tee Connector 55 Type STLH Hood Nut Terminal Connector 56 Alnox ® UG Electrical Joint Compound 58
2 AFLglobal.com 1 (800) 890-8878 11.12.2026 2 Network Underground Alphanumeric Connector Type Index BCKT 53 BCLA-R123, BCLA-P123, BCLA-PL123 36 C 14 CKS 15 CRC, CRC-C 45 CRT 49 CRW 46 DPC 47 DPL 51 DPR 48 HNT 55 LLA-2P1 29 LLA-2P2 28 LLA-2PL123 25 LLA-2PL3 27 LLA-2R123, LLA-2P123 24 LLA-2R3, LLA-2P3 26 MA 12 MIC 11 MIS 16 ML-1 35 ML-PL123 31 ML-PL3 33 ML-R123, ML-P123 30 ML-R2, ML-P2 34 ML-R3, ML-P3 32 NCLA-E 44 NRLA-1 23 NRLA-PL123 20 NRLA-PL3 21 NRLA-R123, NRLA-P123 18 NRLA-R2, NRLA-P2 22 NRLA-R3, NLRA-P3 20 P 13 RL-2 39 RLBC-E 42 RLB-E 37 RLLA-E 43 RLL-E 41 RLM-B 38 RLM-E 40 STC 17 STLH 56
3 AFLglobal.com 1 (800) 890-8878 11.12.2026 3 Network Underground MICON Accessories Type MIC PG 11 Type MA PG 12 Type P PG 13 Type C PG 14 Type CKS PG 15 Type MIS PG 16 Type STC PG 17 Types NRLA-R123, NRLA-P123 PG 18 Type NRLA-PL123 PG 19 Types NRLA-R3, NRLA-P3 PG 20 Type NRLA-PL3 PG 21 Types NRLA-R2, NRLA-P2 PG 22 Type NRLA-1 PG 23 Types LLA- 2R123, LLA-2P123 PG 24 Type LLA-2PL123 PG 25 Types LLA-2R3, LLA-2P3 PG 26 Type LLA-2PL3 PG 27 Type LLA-2P2 PG 28 Type LLA-2P1 PG 29 MICON Limiter Assemblies Types ML-R123, ML-P123 PG 30 Type ML-PL123 PG 31 Types ML-R3, ML-P3 PG 32 Type ML-PL3 PG 33
4 AFLglobal.com 1 (800) 890-8878 11.12.2026 4 Network Underground MICON Limiter Assemblies Types ML-R2, ML-P2 PG 34 Type ML-1 PG 35 Types BCLA-R123, BCLA-P123, BCLA-PL123 PG 36 Type RLB-E PG 37 Type RLM-B PG 38 Type RL-2 PG 39 Type RLM-E PG 40 Type RLL-E PG 41 Type RLBC-E PG 42 Type RLLA-E PG 43 Type NCLA-E PG 44 Types CRC, CRC-C PG 45 Type CRW PG 46 Type DPC PG 47 Type DPR PG 48 Type CRT PG 49 Type DPL PG 51 Type BCKT PG 53 Type HNT PG 55 Type STLH PG 56 Compounds Alnox ® UG Electrical Joint Compound PG 60
5 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00135, Revision 2, 12.5.2025 Specifications are subject to change without notice. 5 Network Underground Of great prominence in the improvements of the Dossert line is the almost complete elimination of the “factory taped joint.” The use of factory taped joints in place of the fully vulcanized and seamless insulation has been at best a poor compromise between economy of manufacture and reliability. Too often have these joints proven defective because of improper fabrication or rough handling before installation. AFL does not make this compromise, and wherever possible fully molds the insulation around the connector without seams of any kind. This feature has been incorporated in all of the MICON and Crab Connectors. Improvements in the insulating materials by the development of MYPAR and MYPRENE natural and synthetic insulations is perhaps of superior insulating and aging qualities greatly extend the useful life, and reliabilities of underground installations. The specifications and physical properties of these insulations are presented herein. In addition to the introduction of a complete line of underground connectors and accessories, AFL offers engineering and manufacturing service for any special requirements in this field. A portion of our engineering department has been organized to respond promptly to inquiries on special fittings and unusual problems which AFL has always considered as important as the regular manufacturing production. Frequently “specials” may not be specials at all, even though they are not catalogued, and may be readily and quickly supplied at nominal cost. The Dossert line of connectors from AFL have been used underground almost since the first underground electrical distribution systems were installed. Early records show that Dossert connectors were used in underground installations dating from 1910. Changes in the industry led to the development and manufacture of a complete line of connectors and fittings for underground use. Research in materials and manufacturing techniques enabled improvements to the Dossert line without affecting standardization and interchangeability. The main emphasis in the development program has been on interchangeability of the connectors and fittings and of their various components. Fortunately, most underground connectors are manufactured to standards established by several public utilities and these standards have gained wide acceptance throughout the country. The advantages of this standardization are great as not only may various components in a system be replaced without concern over the name of the manufacturer, date of manufacture and catalog numbers, but training of personnel and stocking of components are simplified. Compression tools which very often represent a sizeable investment will not be made obsolete. It did not seem wise to introduce radically different connector designs even though present experience would point to some advantage of newer designs. This is an area where maximum reliability is an essential requirement, and where because of standardization and training of installation crews any changes would be disadvantageous. Improvements in underground connectors were, therefore, limited to those changes which would not affect interchangeability. Introduction AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
6 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00135, Revision 2, 12.5.2025 Specifications are subject to change without notice. 6 Network Underground The Dossert MICON from AFL is the basic element of a connector assembly for joining 2 to 18 or more electrical cables where a fully insulated, watertight electrical connection is required. It is essentially a pre-insulated bus bar to which cables are connected by means of mechanical cable receptacles in such a manner as to facilitate insulating the joints and making future changes. Its use lies mainly with secondary distribution networks but is not limited to this application. Use of the MICON eliminates considerable field labor. More reliable connections are obtained as cable crotches are eliminated. The body of the MICON is a copper bus bar of hard drawn high strength copper having an electrical conductivity of not less than 98% I.A.C.S. The bar is of hexagon shape having drilled and tapped holes with contact faces at each outlet position. The bus or core of the connector is covered with high quality molded rubber insulation without seams and with a minimum insulation thickness of 0.220 inches. Holes in the insulation with molded tubular projections are provided at each outlet position. The cable receptacle, either type MA or CKS is inserted through the tubular projection and screwed into the bus core making contact on the threads and on the contact face. The tubular projections permit easy taping with a simple winding motion and this can be done directly over the cable receptacle over a telescoping sleeve. The component which attaches the cable to the MICON is called the cable receptacle. The most popular type, is type MA which is a mechanical connector that is screwed into the body of the MICON and which receives and connects the cable. The cable clamping element is a tapered sleeve which compresses on the conductor as it is driven into the matching tapered hole in the body of the connector as the gland nut is tightened. There is a tremendous overall mechanical advantage in this connector because of the compounding of the mechanical advantage in the screw of the gland nut with the low angle taper of the sleeve. The result is an extremely secure and reliable joint. The tapered sleeve is slotted in such a way to provide minimum resistance to compression and to assure even radial contact pressure on the conductor. The slots are numerous and of narrow width so that a single strand cannot be caught in a slot and prevent proper compression. The inside of the tapered sleeve has carefully designed serrations for maximum efficiency electrically and mechanically. Each sleeve is used for one conductor size only. A broad range of conductor sizes are available and only the tapered sleeve need be changed to accommodate a cable within the range of conductor sizes for a given MA unit. TECH: MICON To install the type MA cable receptacle it is necessary to connect the MA body to the MICON. This is accomplished by inserting the threaded stud of the MA body into the tapped hole in the MICON to the cable receptacle. This is usually done by placing the gland nut and the tapered sleeve on the conductor after the insulation has been stripped. The end of the conductor is then placed in the socket and the gland nut is tightened. It is very important that the tapered sleeve be positioned flush with the end of the conductor. If space does not permit this method of assembly the tapered sleeve and gland nut can be assembled in the connector and the gland nut screwed in until it is just finger tight. Then the end of the conductor is placed in the socket and the tapered sleeve. The cable is measured so that the end will come flush with the end of the tapered sleeve. The gland nut is the tightened with a wrench. An alternate method of connecting the cable to the MICON is by use of the type CKS compression cable receptacle. Similar to the type MA receptacle, the type CKS has a threaded stud which screws into the MICON body. The other end, however, is a compression sleeve in which the cable is inserted and indents made with a standard compression tool. As with all other compression connectors the type CKS cable receptacle cannot be reused or re-adjusted after the indents have been made. The MICON is furnished in six basic styles – MC, MCA, MCB, MCC, MCD, and MCE each with current ratings of 1500, 2000, 2500, and 3000 amperes. The ampere ratings are based upon the maximum current permitted to pass through the minimum cross section of the MICON conducting body. The minimum cross section of the MICON would constitute that section which would be formed if one were to take a saw cut directly across the MICON at the center of one of the outlet positions. By proper orientation of the line and load cables, current carrying capacities considerably greater than the ampere ratings of the MICON can be obtained. The ideal arrangement of cables would be to have a line cable feed an outlet and have a load cable, on the same center line but in the directly opposite, adjacent outlet, conducting current away from the MICON connector. Any arrangement would be to have the feeder and load cables oriented in such a manner so as to cause total current to pass through the minimum cross section of the MICON. Under such an arrangement the total current must not exceed the MICON rating.
7 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00135, Revision 2, 12.5.2025 Specifications are subject to change without notice. 7 Network Underground All of the MICON types of multi-outlet insulated connectors are manufactured with a fully molded insulation. The standard insulating material is Mypar, or compound type GA-20. Mypar is a specially compounded rubber base insulation designed to resist the deteriorating effects of oils, sulphurous and organic gases as well as seepage water containing the types of contaminates found in sewer systems. Mypar has been chosen as the general insulation for the MICON connectors because of the following beneficial qualities: 1. High dielectric strength 2. High mechanical strength 3. High resistance to abrasion 4. Good resistance to action of alkalis 5. Good resistance to moderately concentrated solutions of common acids. 6. Relatively high resistance to deteriorating effects of oil. Will withstand occasional immersion in oil without any del - eterious effects. 7. Long age of life under normal operating temperatures found in the underground systems. Like any rubber bearing compound the life expectancy of Mypar is reduced at elevated temperatures. Mypar can be raised to approximately 95 degrees Celsius before deterioration will occur at an accelerated rate. Mypar maintains a relatively stable Durom - eter hardness throughout its normal temperature operating range. At extremely low temperatures (approximately 0 degrees Celsius) Mypar will become more rigid but will maintain an adequate degree of flexibility. There are applications where MICON connectors are subject to frequent immersion in waters containing relatively large amounts of oil or higher concentration of acids, alkalis, and hydro-carbons. For these applications Myprene, or compound GA-62 is recommended as the insulating material. Myprene is a neoprene base compound with extremely high resistance to oil or acid container water. In addition, can be used at temperatures up to 145 degrees Celsius for periods of short duration without any measurable deterioration. The specifications and minimum physical properties of both compounds are presented in tables A and B. Table A — Specification for Mypar Insulation Mypar (Compound GA-20) is the standard rubber insulating compound used on all of the MICON components. TECH: MICON Insulation Parameter Value Rubber Content 60% by weight Specific Gravity 1 16 Durometer Hardness 55 Water absorption after immersion in water at 70°F for 24 hours 0 23% Tensile Strength 3000 lbs per sq in Elongation at Rupture 550% Modification of Properties after immersion in ASTM oil #1 for 48 hour period at 70°F Tensile Strength 1 3% Loss Elongation at Rupture Zero Volume Swelling 5% Gain Durometer Hardness Minus 1 Modification of Properties after 96 hour oxygen bomb test at 158°F Tensile Strength 14 4% Loss Elongation at Rupture 17 9% Loss Durometer Plus 3 Electrical Characteristics of Insulation as molded on connector Effect of rising voltage breakdown test showed 2000 ampere capacity type MC MICON to run between 35 and 40 kV Test run dry with MICON covered with powdered zinc Effect of rising voltage breakdown test with same size connector immersed in a 3% Saline solution at 70°F average temperature showed MICON breakdown voltages to run 15-18 kV after 30 weeks
8 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00135, Revision 2, 12.5.2025 Specifications are subject to change without notice. 8 Network Underground Table B—Specification for MYPRENE Insulation MYPRENE (Compound GA-62) is the neoprene insulating compound used when specified in place of MYPAR for more severe applications on MICON components. TECH: MICON Insulation (continued) Parameter Value Rubber Content None Neoprene Content 52% Neoprene by weight Specific Gravity 1 35 Durometer Hardness 60 Water absorption after immersion in water at 70°F for 24 hours 1 12% Tensile Strength 2500 lbs per sq in Elongation at Rupture 400% Modification of Properties after immersion in ASTM oil #1 for 48 hour period at 70°F Tensile Strength 19% Gain Elongation at Rupture 7% Gain Volume Swelling 1 8% Gain Durometer Hardness Minus 1 Modification of Properties after 96 hour oxygen bomb test at 158°F Tensile Strength 11 9% Loss Elongation at Rupture 14% Loss Durometer Hardness Plus 8 Electrical Characteristics of Insulation as molded on connector Effect of rising voltage breakdown test showed 2000 ampere capacity type MC MICON to run between 20 and 25 kV Test run dry with MICON covered with powdered zinc Effect of rising voltage breakdown test with same size connector immersed in a 3% Saline solution at 70°F average temperature showed MICON breakdown voltages to run 12-17 kV
9 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00135, Revision 2, 12.5.2025 Specifications are subject to change without notice. 9 Network Underground For making proper selection of a MICON connector requiring a cable outlet connection larger than 600 MCM, take the following steps: A. Choose the desired catalog number from the MICONS shown on pages 10 to 15. B. Using Table 1 select the outlet size number required for the size cable employed. C. Using Table 2 determine the available outlet positions for cables larger than 600 MCM. D. Specify your MICON connector by the following order example: Assume that an 8 outlet MICON connector in type MCD for 2000 ampere current rating is required. This would call for catalog number MCD 200-8. Let it further be assumed that cable sizes will be required for outlets in accordance with the following schedule: The wide overlapping of conductor sizes for outlet sizes #63 and #88 permits one to use a #88 outlet with any cable size within the range of the #63 outlet. As future load requirements necessitate larger cables one can connect to the outlet the #88 outlet cable sizes from our 600 MCM to 1000 MCM inclusive. Where no future expansion of load requirements is anticipated it is most economical to select the #63 outlet. For all MICONS and insulating accessories MYPAR insulation is used as standard procedure. To specify MYPRENE insulation add the suffix “-N” to the catalog number of any part for which MYPRENE insulation is desired. All of the Dossert MICON connectors are furnished, unless otherwise specifies, with #63 size outlets as standard connector units. There are also available outlet sizes #88 and #112 which permit use of larger cable sizes in the outlet positions. Table 1 shows the outlet size number, with the corresponding range of specific cable sizes and the receptacle stud mounting thread size. TECH: MICON Ordering Data Table 1 Outlet Size No. Range of Specific Cable Sizes Handled by Outlet Stud Mounting Thread Size Min. Max. 63 #6 Str 600 MCM 5/8 - 18 NF2 88 #6 Str 1000 MCM 7/8 - 14 NF2 112 1250 MCM 2000 MCM 1 1/8 - 12 NF2 Outlet sizes larger than #63 may be used to advantage in meeting higher load conditions for present installations or for the planning of higher loads on future installations. Table 2 shows the available outlet sizes and their position for the various ampere capacity MICONS. Table 2 Micon Current Rating (amperes) Positions A and/or R Positions All Remaining 1500 #63 or #88 #63 2000 #63, #88, or #112 #63 or #88 2500 #63, #88, or #112 #63, #88, or #112 3000 #63, #88, or #112 #63, #88, or #112 Table 3 Outlet Position Cable Size A 1500 MCM B 750 MCM C 800 MCM R 750 MCM Order for Type MCD should be written: MCD 200-8 Outlet Positions Outlet Size A #112 B, C, R #88 Remaining Outlets #63
10 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00135, Revision 2, 12.5.2025 Specifications are subject to change without notice. 10 Network Underground The Dossert Limiter from AFL is designed with a fusible element which is held to close tolerances to insure a close consistency of operation on all production made elements of any given size. The fusible section provides a time lag on intermittent overloads and does not open the circuit as does a common fuse. The fusible section is designed to sustain moderate overloads but to burn clear and open the circuit under such heavy overloads or faults which would be of a magnitude sufficient to cause damage to the cable insulation. The time-current characteristics are in consequences derived from the insulation damage characteristics of the cable. Since the insulation damage characteristics of rubber covered and oil-impregnated, paper cable are Limiter Fusing Characteristics practically identical, the curves on the chart constitute the damage characteristics for both types of cable. The curves resolving the time-current characteristics of Limiters and the insulation damage characteristics of cables found on the chart represent those sizes commonly used in underground network systems. The limiter fusing characteristics shown on the chart apply to all types of limiter designs whether they be straight Limiters, Limiter lugs or any Limiter modification designed for the particular conductor size shown. AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
11 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00108, Revision 2, 11.5.2025 Specifications are subject to change without notice. 11 Network Underground A coupling for joining Micon connectors on end. The special engaging feature of the coupling permits the outlets of each unit, when joined in series, to assume any position about the center axis. The small exposed area makes possible a neatly taped junction. Coupling may also be used on side outlets for different assembled configurations. MICON Coupling Type MIC Ordering Information Catalog Number Current Rating Amperes Number of Outlets Stud Size (S) Dimensions in Inches L H* MIC63 63 1275 5/8 - 18 NF-2 4 3/16 1 5/16 MIC88 88 1700 7/8 - 14 NF-2 4 5/16 1 5/8 MIC112 112 2125 1 1/8 - 12 NF-2 4 11/16 2 1/8 L LOCK NUT S H S * Across hexagonal flats AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
12 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00099, Revision 3, 10.27.2025 Specifications are subject to change without notice. 12 Network Underground A high strength, high conductivity cable receptacle for securing cables electrically and mechanically to the MICON outlet positions. Each size accommodates a wide range of cable sizes from maximum to a selected minimum size through use of Type C tapered compression sleeves. The turned edges, compactness, and close fit to the MICON outlets make possible a neat and easy taping. Type MA Cable Receptacle Ordering Information Catalog Number Maximum Cable Size Stud Size (S) Outlet Size* Dimensions in Inches A B C** D** L MA21 4/0 STR 5/8 - 18 NF-2 63 1 7/16 9/16 1 1/8 7/8 3 13/32 MA25 250 MCM 5/8 - 18 NF-2 63 1 11/16 9/16 1 3/16 15/16 3 21/32 MA30 300 MCM 5/8 - 18 NF-2 63 1 3/4 9/16 1 1/4 1 3 23/32 MA40 400 MCM 5/8 - 18 NF-2 63 1 13/16 9/16 1 3/8 1 1/8 3 25/32 MA50 500 MCM 5/8 - 18 NF-2 63 1 7/8 9/16 1 1/2 1 1/4 3 27/32 MA60 600 MCM 5/8 - 18 NF-2 63 1 15/16 9/16 1 1/2 1 1/4 3 29/32 MA80 800 MCM 7/8 - 14 NF-2 88 2 3/16 3/4 1 13/16 1 1/2 4 11/32 MA100 1000 MCM 7/8 - 14 NF-2 88 2 1/2 3/4 1 15/16 1 5/8 4 21/32 MA125 1250 MCM 1 - 1/8 - 12 NF-2 112 2 9/16 7/8 2 1/4 2 4 27/32 MA150 1500 MCM 1 - 1/8 - 12 NF-2 112 2 3/4 7/8 2 3/8 2 1/8 5 1/32 MA175 1750 MCM 1 - 1/8 - 12 NF-2 112 2 7/8 7/8 2 1/2 2 1/4 5 5/32 MA200 2000 MCM 1 - 1/8 - 12 NF-2 112 3 7/8 2 5/8 2 3/8 5 9/32 D C S B A L * MICON Outlet Size ** Dimensions across hexagonal flats Note • For Lock Washer, add "-LW" to end of catalog number AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
13 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00118, Revision 2, 11.10.2025 Specifications are subject to change without notice. 13 Network Underground AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials All Micon connectors are furnished with Mypar plugs, accommodating 25% of the outlets. Myprene plugs can also be furnished. To specify, suffix catalog number with -N. Type P plugs make a snug fit on all outlet positions and provide a convenient means for sealing unused outlets. MICON Outlet Plugs Type P Ordering Information Catalog Number Outlet Size Dimensions in inches C D H L T P63 63 1 1/2 1 5/32 1 1/8 1 9/16 7/16 P88 88 1 13/16 1 13/32 1 1/4 1 11/16 7/16 P112 112 2 1/8 1 5/8 1 1/4 1 3/4 1/2 C D H T L
14 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00072, Revision 2, 11.10.2025 Specifications are subject to change without notice. 14 Network Underground Designed for use with type MA cable receptacles. Each size is machined with close tolerances for a specific cable size. A low angle of taper provides for greater mechanical advantage effecting a high clamping action. Internal serrations further add to the electrical contact efficiency and secureness of grip. Type C Tapered Compression Sleeve Ordering Information Cable Size D in inches Sleeve Catalog Nos. for Use with Cable Receptacle No. MA-21 MA-25 MA-30 MA-40 MA-50 MA-60 MA-80 MA-100 MA-125 MA-150 MA-175 MA-200 6 STR 0 184 C21-2 C25-2 C30-2 4 STR 0 232 C21-4 C25-4 C30-4 2 STR 0 292 C21-6 C25-6 C30-6 C40-6 C50-6 1 STR 0 332 C21-8 C25-8 C30-8 C40-8 C50-8 1/0 STR 0 372 C21-10 C25-10 C30-10 C40-10 C50-10 2/0 STR 0 419 C21-13 C25-13 C30-13 C40-13 C50-13 3/0 STR 0 47 C21-17 C25-17 C30-17 C40-17 C50-17 4/0 STR 0 528 C21-21 C25-21 C30-21 C40-21 C50-21 250 MCM 0 575 C25-25 C30-25 C40-25 C50-25 C60-25 300 MCM 0 63 C30-30 C40-30 C50-30 C60-30 350 MCM 0 681 C40-35 C50-35 C60-35 C80-35 400 MCM 0 728 C40-40 C50-40 C60-40 C80-40 500 MCM 0 813 C50-50 C60-50 C80-50 C100-50 550 MCM 0 855 C60-55 C80-55 C100-55 600 MCM 0 893 C60-60 C80-60 C100-60 650 MCM 0 929 C80-65 C100-65 700 MCM 0 964 C80-70 C100-70 750 MCM 0 998 C80-75 C100-75 C125-75 800 MCM 1 031 C80-80 C100-80 C125-80 850 MCM 1 062 C100-85 C125-85 900 MCM 1 094 C100-90 C125-90 950 MCM 1 123 C100-95 C125-95 1000 MCM 1 152 C100-100 C125-100 C150-100 1250 MCM 1 289 C125-125 C150-125 C175-125 1500 MCM 1 412 C150-150 C175-150 C200-150 1750 MCM 1 526 C175-175 C200-175 2000 MCM 1 632 C200-200 D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
15 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00078, Revision 2, 11.12.2025 Specifications are subject to change without notice. 15 Network Underground A compression type receptacle for securing cables electrically and mechanically to the MICON outlet positions. For a number of cable sizes, other than listed, type DR corrugated reducing adapters can be used to advantage with catalog numbers CKS21-63 and CKS50-63. Type CKS Compression Receptacle Ordering Information Catalog Number Maximum Cable Size Outlet Size Stud Size (S) No. of Indents Dimensions in inches A B C D L CKS21-63 4/0 63 5/8-18 1 1 5/8 9/16 11/16 15/16 4 5/8 CKS25-63 250 63 5/8-18 1 1 5/8 9/16 3/4 15/16 4 5/8 CKS30-63 300 63 5/8-18 2 2 9/16 13/16 15/16 5 CKS35-63 350 63 5/8-18 2 2 9/16 7/8 15/16 5 CKS40-63 400 63 5/8-18 2 2 1/8 9/16 15/16 15/16 5 1/8 CKS50-63 500 63 5/8-18 2 2 1/4 9/16 1 1/16 15/16 5 1/4 CKS60-63 600 63 5/8-18 2 2 11/16 9/16 1 3/16 15/16 5 11/16 CKS70-88 700 88 7/8-14 2 2 13/16 3/4 1 1/4 1 1/4 6 1/4 CKS75-88 750 88 7/8-14 2 2 7/8 3/4 1 5/16 1 1/4 6 5/16 CKS80-88 800 88 7/8-14 2 2 15/16 3/4 1 3/8 1 1/4 6 3/8 CKS90-88 900 88 7/8-14 2 2 15/16 3/4 1 7/16 1 1/4 6 3/8 CKS100-88 1000 88 7/8-14 2 3 3/4 1 1/2 1 1/4 6 7/16 CKS125-112 1250 112 1 1/8-12 2 3 3/16 7/8 1 3/4 1 3/4 6 7/8 CKS150-112 1500 112 1 1/8-12 2 3 13/16 7/8 1 7/8 1 3/4 6 7/8 CKS175-112 1750 112 1 1/8-12 2 3 7/16 7/8 2 1 3/4 7 1/8 CKS200-112 2000 112 1 1/8-12 2 3 7/16 7/8 2 1/8 1 3/4 7 1/8 D C A L S B AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
16 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00109, Revision 2, 11.12.2025 Specifications are subject to change without notice. 16 Network Underground An insulating sleeve to facilitate the taping of the MICON outlet. The sleeve makes a snug fit over the MICON outlet as well as the cable insulation. A positive seal is established by several turns of tape at each end of the sleeve. When ordering, specify the catalog number or size of MICON, the cable receptacle size type MA, and the diameter of insulation over cable. For largest sleeve grouping, spacings of MICON outlets must be ascertained to establish feasibility of using sleeves in adjacent positions. Type MIS Insulating Sleeve Ordering Information Catalog Number For Use with Receptacles Fig. No. Dimensions in inches D OD L MIS25-30-56 MA-21 MA-25 MA-30 1 9/16 1 15/16 4 13/16 MIS25-30-75 1 3/4 1 15/16 4 13/16 MIS25-30-88 1 7/8 1 15/16 4 13/16 MIS25-30-100 1 1 1 15/16 4 13/16 MIS25-30-112 1 1 1/8 1 15/16 4 13/16 MIS25-60-100 MA-40 MA-50 MA-60 1 1 2 3/16 5 1/4 MIS25-60-112 1 1 1/8 2 3/16 5 1/4 MIS25-60-125 1 1 1/4 2 3/16 5 1/4 MIS25-60-138 1 1 3/8 2 3/16 5 1/4 MIS50-80-125 MA-80 1 1 1/4 2 23/32 5 3/4 MIS50-80-138 1 1 3/8 2 23/32 5 3/4 MIS50-80-150 1 1 1/2 2 23/32 5 3/4 MIS50-80-163 1 1 5/8 2 23/32 5 3/4 MIS50-80-175 1 1 3/4 2 23/32 5 3/4 MIS50-100-125 MA-100 2 1 1/4 2 23/32 7 1/4 MIS50-100-138 2 1 3/8 2 23/32 7 1/4 MIS50-100-150 2 1 1/2 2 23/32 7 1/4 MIS50-100-163 2 1 5/8 2 23/32 7 1/4 MIS50-100-175 2 1 3/4 2 23/32 7 1/4 MIS80-200-175 MA-125 MA-150 MA-175 MA-200 2 1 3/4 3 7/16 9 3/8 MIS80-200-188 2 1 7/8 3 7/16 9 3/8 MIS80-200-200 2 2 3 7/16 9 3/8 MIS80-200-212 2 2 1/8 3 7/16 9 3/8 MIS80-200-225 2 2 1/4 3 7/16 9 3/8 OD D L Fig. 1 OD D L Fig. 2 AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
17 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00130, Revision 2, 11.12.2025 Specifications are subject to change without notice. 17 Network Underground A straight line coupler for joining two cables on end. The symmetry and compact design render the connector easy to tape. A high mechanical advantage ensures a sound mechanical and electrical connection for trouble free operation. Type STC Cable Coupler Ordering Information Catalog Number Cable Size Cable Diameter Dimensions in inches E F L LB STC2 6 STR 0 184 9/16 7/16 2 5/16 1 1/2 STC4 4 STR 0 232 5/8 1/2 2 5/16 1 1/2 STC6 2 STR 0 292 11/16 9/16 2 3/4 1 7/8 STC8 1 STR 0 332 13/16 5/8 3 2 STC10 1/0 STR 0 372 15/16 3/4 3 3/8 2 1/8 STC13 2/0 STR 0 419 1 13/16 3 1/2 2 1/4 STC17 3/0 STR 0 47 1 13/16 3 3/4 2 1/2 STC21 4/0 STR 0 528 1 1/8 7/8 3 13/16 2 5/8 STC25 250 MCM 0 575 1 3/16 15/16 4 2 3/4 STC30 300 MCM 0 63 1 1/4 1 4 3/8 3 STC35 350 MCM 0 681 1 3/8 1 1/8 5 1/8 3 3/4 STC40 400 MCM 0 728 1 3/8 1 1/8 5 3/16 3 13/16 STC50 500 MCM 0 813 1 1/2 1 1/4 5 1/4 3 7/8 STC60 600 MCM 0 893 1 9/16 1 5/16 5 3/4 4 STC70 700 MCM 0 964 1 3/4 1 7/16 6 4 1/4 STC75 750 MCM 0 998 1 13/16 1 1/2 6 1/2 4 5/8 STC80 800 MCM 1 031 1 13/16 1 1/2 6 5/8 4 3/4 STC90 900 MCM 1 094 1 15/16 1 5/8 6 3/4 4 7/8 STC100 1000 MCM 1 152 1 13/16 1 5/8 7 1/4 5 3/16 STC125 1250 MCM 1 289 2 1/4 2 8 5 5/8 STC150 1500 MCM 1 412 2 3/8 2 1/8 8 3/4 6 1/8 STC175 1750 MCM 1 526 2 1/2 2 1/4 9 1/4 6 1/2 STC200 2000 MCM 1 632 2 5/8 2 3/8 10 7 F L LB E AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
18 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00146, Revision 2, 11.12.2025 Specifications are subject to change without notice. 18 Network Underground A cable coupler which serves as both a fuse and connector. The fusible element has a time-current characteristic which will enable it to clear faults severe enough to cause cable insulation damage. Unlike a fuse, the limiter will not clear a circuit on system overloads. Types NRLA-R123, NRLA-P123 Limiter Link Assembly Ordering Information Catalog Number Cable Size Indents in Cable Socket Dia. Over Cable Insulation Dimensions in inches For Rubber Insulated Cable For Paper* Insulated Cable L O.D. NRLA21-R123 NRLA21-P123 4/0 1 Diameter over cable insulation to be specified on order 12 7/8 2 NRLA25-R123 NRLA25-P123 250 MCM 1 12 7/8 2 NRLA30-R123 NRLA30-P123 300 MCM 2 13 5/8 2 1/4 NRLA35-R123 NRLA35-P123 350 MCM 2 13 5/8 2 1/4 NRLA40-R123 NRLA40-P123 400 MCM 2 13 5/8 2 1/4 NRLA50-R123 NRLA50-P123 500 MCM 2 16 2 7/16 NRLA75-R123 NRLA75-P123 750 MCM 2 16 2 5/8 L O D 1 2 3 * Closed end of sockets are sealed to make sockets oil tight Elements Type No. Name NRLA -1 1 Insulating Sleeve NRLA-R2 2 Shell NRLA-P2 NRLA-R3 3 Limiter Link NRLA-P3 AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
19 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00108, Revision 2, 11.5.2025 Specifications are subject to change without notice. 19 Network Underground A cable coupler which serves as both a fuse and connector. The fusible element will clear the line on faults or overloads servere enough to cause cable damage. The longer cable sockets offer greater taping area for establishing an oil sealed joint.* Type NRLA-PL123 Long Limiter Link Assembly for Paper Insultated Cable Ordering Information Catalog Number Cable Size iIndents in Cable Socket Dia. over Cable Insulation Dimensions in inches L O.D. NRLA21-PL123 4/0 1 Diameter over cable insulation to be specified on order 12 7/8 2 NRLA25-PL123 250 MCM 1 12 7/8 2 NRLA30-PL123 300 MCM 2 13 5/8 2 1/4 NRLA35-PL123 350 MCM 2 13 5/8 2 1/4 NRLA40-PL123 400 MCM 2 13 5/8 2 1/4 NRLA50-PL123 500 MCM 2 16 2 7/16 NRLA75-PL123 750 MCM 2 16 2 5/8 L O D 1 2 3 * Closed end of sockets are sealed to make sockets oil tight Elements Type No. Name NRLA -1 1 Insulating Sleeve NRLA-P2 2 Shell NRLA-PL3 3 Limiter Link AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
20 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00147, Revision 2, 11.12.2025 Specifications are subject to change without notice. 20 Network Underground The limiter link has a dual function of serving as a connecting coupler as well as a fuse. The fusible section determines the time-current characteristics of each size. This is made to close tolerances to insure consistent conformity with the fusing time-current curves. Types NRLA-R3, NLRA-P3 Limiter Link L B B A Ordering Information Catalog Number Cable Size Indents in Cable Socket Dimensions in inches For Rubber Insulated Cable For Paper* Insulated Cable A** B L NRLA21-R3 NRLA21-P3 4/0 STR 1 11/16 1 3/4 6 3/8 NRLA25-R3 NRLA25-P3 250 MCM 1 3/4 1 7/8 6 3/8 NRLA30-R3 NRLA30-P3 300 MCM 2 13/16 2 6 3/4 NRLA35-R3 NRLA35-P3 350 MCM 2 7/8 2 6 3/4 NRLA40-R3 NRLA40-P3 400 MCM 2 31/32 2 1/8 7 NRLA50-R3 NRLA50-P3 500 MCM 2 1 1/16 2 3/4 8 3/4 NRLA75-R3 NRLA75-P3 750 MCM 2 1 5/16 2 3/4 9 * Closed end of sockets are sealed to make sockets oil tight ** Diameter AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
21 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00116, Revision 3, 11.12.2025 Specifications are subject to change without notice. 21 Network Underground The long limiter link has a dual function of serving as a connecting coupler as well as a fuse. The fusible section determines the time-current characteristics of each size. This is made to close tolerances to insure consistent conformity with the fusing time-current curves. The limiter will not clear the circuit on system overloads but will clear the circuit on faults severe enough to cause cable insulation damage. Type NRLA-PL3 Long Limiter Link for Paper Insulated Cable* L B B A Ordering Information Catalog Number Cable Size Indents in Cable Cocket Dimensions in inches A** B L NRLA21-PL3 4/0 STR 1 11/16 3 8 7/8 NRLA25-PL3 250 MCM 1 3/4 3 1/8 8 7/8 NRLA30-PL3 300 MCM 2 13/16 3 1/2 9 5/8 NRLA35-PL3 350 MCM 2 7/8 3 1/2 9 5/8 NRLA40-PL3 400 MCM 2 31/32 3 1/2 9 5/8 NRLA50-PL3 500 MCM 2 1 1/16 4 1/4 11 1/2 NRLA75-PL3 750 MCM 2 1 5/16 4 1/4 11 3/4 * Closed end of sockets are sealed to make sockets oil tight ** Diameter AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
22 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00117, Revision 4, 11.12.2025 Specifications are subject to change without notice. 22 Network Underground An arc proof shell of molded composition provided with a system of cavities and heat confining barriers. The shell assembly permits fusible section of limiter to melt and clear line without causing damage to surrounding insulation by restraining and confining the arc and insolating the resulting heat. Types NRLA-R2, NRLA-P2 Limiter Shell for Use with Limiter Link Types NRLA-R3, NRLA-P3, and NRLA-PL3 Ordering Information Catalog Number Cable Range Dimensions in inches For Rubber Insulated Cable For Paper* Insulated Cable A L NRLA25-R2 NRLA25-P2 4/0 STR-250 MCM 1 1/2 6 13/16 NRLA40-R2 NRLA40-P2 300 MCM - 400 MCM 1 3/4 7 9/16 NRLA50-R2 NRLA50-P2 500 MCM 1 7/8 9 7/16 NRLA75-R2 NRLA75-P2 750 MCM 2 1/8 8 7/8 * For use with regular or long limiter link types NRLA-P3 and NRLA-PL3 Material Asbestite Cement, Varnish Coated L A AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
23 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00114, Revision 3, 11.12.2025 Specifications are subject to change without notice. 23 Network Underground A MYPAR molded insulating sleeve for use with limiter link assemblies. This two section unit is provided with interlocking ends to form a smooth junction. Its use simplifies taping and improves the accessibility to the enclosed limiter. Type NRLA-1 Insulating Sleeve for Types NRLA-P, NRLA-R, and NRLA-PL Limiter Link Assemblies Ordering Information Catalog Number Cable Range Diameter Over Cable Insulation (I.D.) Dimensions in inches L O.D. NRLA25-1 4/0 STR - 250 MCM Diameter over cable insulation to be specified on order 12 7/8 2 NRLA40-1 300 MCM - 400 MCM 13 5/8 2 1/4 NRLA50-1 500 MCM 16 2 7/16 NRLA75-1 750 MCM 16 1/4 2 5/8 L O D I D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
24 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00141, Revision 2, 11.12.2025 Specifications are subject to change without notice. 24 Network Underground A cable terminal which serves as both a fuse and connector. The fusible element has a time-current characteristic which will enable it to clear faults severe enough to cause cable insulation damage. Unlike a fuse, the limiter will not clear a circuit on system overloads of short period. Types LLA-2R123, LLA-2P123 Limiter Terminal Assembly Ordering Information Catalog Number Cable Size No. of Indents Dimensions in inches For Rubber Insulated Cable For Paper Insulated Cable* A C D L H X O.D. LLA21-2R123 LLA21-2P123 4/0 STR 1 1 2 3/16 Diameter over cable insulation to be specified on order 11 5/8 7/8 7/16 2 LLA25-2R123 LLA25-2P123 250 MCM 1 1 3/32 2 3/16 11 5/8 7/8 7/16 2 LLA30-2R123 LLA30-2P123 300 MCM 2 1 3/16 2 5/16 13 1/4 1 1/2 2 7/16 LLA35-2R123 LLA35-2P123 350 MCM 2 1 9/32 2 5/16 13 1/4 1 1/2 2 7/16 LLA40-2R123 LLA40-2P123 400 MCM 2 1 13/32 2 5/16 13 1/4 1 1/2 2 7/16 LLA50-2R123 LLA50-2P123 500 MCM 2 1 1/2 2 3/4 13 5/8 1 1/2 2 7/16 LLA75-2R123 LLA75-2P123 750 MCM 2 1 15/16 2 3/4 13 5/8 1 1/2 2 7/16 * Closed end of sockets are sealed to make sockets oil tight Elements Type No. Name LLA-2P1 1 Insulating Sleeve LLA-2P2 2 Shell LLA-2R3 OR LL1-2P3 3 Limiter Terminal C A 1 1 / 4 ∅ 7 / 16 D H L O DIA 1 O DIA 2 3 X AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
25 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00096, Revision 2, 11.12.2025 Specifications are subject to change without notice. 25 Network Underground A cable terminal which serves as both a fuse and a connector. The fusible element has a time-current characteristic which will enable it to clear faults severe enough to cause cable insulation damage. Unlike a fuse, the limiter will not clear a circuit on system overloads of short period. Type LLA-2PL123 Long Limiter Terminal Assembly for Paper Insulated Cable* Ordering Information Catalog Number Cable Size No. of Indents Dimensions in inches A C D L H X O.D. LLA21-2PL123 4/0 STR 1 1 2 3/16 Diameter over cable insulation to be specified on order 11 5/8 7/8 7/16 2 LLA25-2PL123 250 MCM 1 1 3/32 2 3/16 11 5/8 7/8 7/16 2 LLA30-2PL123 300 MCM 2 1 3/16 2 5/16 13 1/4 1 1/2 2 7/16 LLA35-2PL123 350 MCM 2 1 9/32 2 5/16 13 1/4 1 1/2 2 7/16 LLA40-2PL123 400 MCM 2 1 13/32 2 5/16 13 1/4 1 1/2 2 7/16 LLA50-2PL123 500 MCM 2 1 1/2 2 3/4 13 5/8 1 1/2 2 7/16 LLA75-2PL123 750 MCM 2 1 15/16 2 3/4 13 5/8 1 1/2 2 7/16 * Closed end of sockets are sealed to make sockets oil tight C A 1 1 / 4 ∅ 7 / 16 D 1 2 3 H L O D X Elements Type No. Name LLA-2P1 1 Insulating Sleeve LLA-2P2 2 Shell LLA-2PL3 3 Long Limiter Terminal AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
26 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00142, Revision 2, 11.13.2024 Specifications are subject to change without notice. 26 Network Underground AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials The limiter terminal acts as a cable terminal as well as a current limiting fuse. The fusible section is made to close tolerances to insure consistent conformity with the fusing time-current curves. The limiter terminal will clear on severe loads or faults but will not clear on system overloads of short period. Types LLA-2R3, LLA-2P3 Limiter Terminal Ordering Information Catalog Number Cable Size No. of Indents Dimensions ininches For Rubber Insulated Cable For Paper* Insulated Cable A B C H L O T X LLA21-2R3 LLA21-2P3 4/0 STR 1 1 1 7/8 2 3/16 7/8 8 1/4 11/16 5/32 7/16 LLA25-2R3 LLA25-2P3 250 MCM 1 1 3/32 1 7/8 2 3/16 7/8 8 1/4 3/4 5/32 7/16 LLA30-2R3 LLA30-2P3 300 MCM 2 1 3/16 2 2 5/16 1 8 7/8 13/16 3/16 1/2 LLA35-2R3 LLA35-2P3 350 MCM 2 1 9/32 2 2 5/16 1 8 7/8 7/8 3/16 1/2 LLA40-2R3 LLA40-2P3 400 MCM 2 1 13/32 2 1/8 2 5/16 1 9 31/32 3/16 1/2 LLA50-2R3 LLA50-2P3 500 MCM 2 1 1/2 2 5/8 2 3/4 1 10 1 1/16 7/32 1/2 LLA75-2R3 LLA75-2P3 750 MCM 2 1 15/16 2 5/8 2 3/4 1 10 1 5/16 1/4 1/2 * Closed end of sockets are sealed to make sockets oil tight C A 1 1 / 4 ∅ 7 / 16 B X H L O DIA T
27 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00097, Revision 2, 11.13.2025 Specifications are subject to change without notice. 27 Network Underground AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials The limiter terminal acts as a cable terminal as well as a current limiting fuse. The fusible section is made to close tolerances to insure consistent conformity with the fusing time-current curves. The limiter terminal will clear on severe loads or faults but will not clear on system overloads of short period. Type LLA-2PL3 Long Limiter Terminal for Paper Insulated Cable* Ordering Information Catalog Number Cable Size No. of Indents Dimensions in inches A B C H L O ST X LLA21-2PL3 4/0 STR 1 1 3 5/8 2 3/16 7/8 10 11/16 5/32 7/16 LLA25-2PL3 250 MCM 1 1 3/32 3 5/8 2 3/16 7/8 10 3/4 5/32 7/16 LLA30-2PL3 300 MCM 2 1 3/16 3 3/4 2 5/16 1 10 5/8 13/16 3/16 1/2 LLA35-2PL3 350 MCM 2 1 9/32 3 3/4 2 5/16 1 10 5/8 7/8 3/16 1/2 LLA40-2PL3 400 MCM 2 1 13/32 3 7/8 2 5/16 1 10 3/4 31/32 3/16 1/2 LLA50-2PL3 500 MCM 2 1 1/2 4 1/4 2 3/4 1 11 3/4 1 1/16 7/32 1/2 LLA75-2PL3 750 MCM 2 1 15/16 4 1/4 2 3/4 1 11 3/4 1 5/16 1/4 1/2 * Closed end of sockets are sealed to make sockets oil tight C 1 1 / 4 B X H L O D T A
28 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00095, Revision 2, 11.13.2025 Specifications are subject to change without notice. 28 Network Underground A composition molded shell consisting of two symmetrical halves assembled with machine screws and nuts. Internal cavities and heat confining barriers permit fusible section of limiter to clear circuit without damage to surrounding insulation. Type LLA-2P2 Limiter Terminal Shell for Use with Limiter Terminal Assembly Types LLA-2R123, LLA-2PL, LLA-2P123, and LLA-2PL123 Ordering Information Catalog Number Cable Range Dimensions in inches D-Diameter L LLA25-2P2 4/0 STR - 250 MCM 1 1/2 5 3/4 LLA50-2P2 300 MCM - 500 MCM 1 7/8 7 1/16 LLA75-2P2 750 MCM 1 7/8 7 1/16 D L AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
29 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00094, Revision 2, 11.13.2025 Specifications are subject to change without notice. 29 Network Underground AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials A MYPAR molded insulating sleeve for use with limiter terminal assemblies. Designed to provide a close fit over shell type LLA-2P2 and specified cable insulation. Its use simplifies taping and improves the accessibility to and easy replacement of a blown limiter. Type LLA-2P1 Limiter Terminal Insulating Sleeve for Use with Types LLA-2R123, LLA-2P123, and LLA-2PL123 Ordering Information Catalog Number Cable Range Dimensions in inches D L I.D. LLA25-2P1 4/0 STR - 250 MCM 2 9 * LLA75-2P1 300 MCM - 500 MCM 2 7/16 10 1/2 * D L I D * Diameter over cable insulation to be specified on order
30 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00143, Revision 2, 11.13.2025 Specifications are subject to change without notice. 30 Network Underground The MICON limiter assembly is designed to establish a fusible connecting point at a MICON outlet. The cable is simply installed by making a compression connection on the socket end. The MICON connecting end is then secured through use of the cable receptacle Type MA and tapered compression sleeve Type C. MICON limiters which have cleared a faulted or over loaded circuit can be readily replaced. Types ML-R123, ML-P123 MICON Limiter Assembly Ordering Information Catalog Number Cable Size Recommended MICON Outlet Connection Indents in Cable Socket Dimensions in inches For Rubber Insulated Cable* For Paper Insulated Cable Cable Receptacle Compression Sleeve D L O.D. ML21-R123 ML21-P123 4/0 STR MA-21 C21-21 1 Diameter over cable insulation to be specified on order 9 7/8 1 7/8 ML25-R123 ML25-P123 250 MCM MA-25 C25-25 1 9 7/8 1 7/8 ML30-R123 ML30-P123 300 MCM MA-30 C30-30 2 10 3/8 2 3/16 ML35-R123 ML35-P123 350 MCM MA-40 C40-35 2 10 3/8 2 3/16 ML40-R123 ML40-P123 400 MCM MA-40 C40-40 2 10 3/8 2 3/16 ML50-R123 ML50-P123 500 MCM MA-50 C50-50 2 11 3/4 2 3/8 ML75-R123 ML75-P123 750 MCM MA-50-88 C50-50 2 12 1/4 2 9/16 * Closed end of sockets are sealed to make sockets oil tight Elements Type No. Name ML-1 1 Insulating Sleeve ML-R2 2 Shell ML-P2 ML-R3 3 Limiter ML-P3 L D 2 1 3 O D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
31 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00111, Revision 2, 11.13.2025 Specifications are subject to change without notice. 31 Network Underground The MICON long limiter assembly is designed to establish a fusible connecting point at a MICON outlet for oil-filled paper insulated cable. The cable is simply installed by making a compression connection on the socket end and by a cable receptacle and tapered sleeve, types MA and C, on the MICON end. MICON Limiters which have cleared a faulted or over loaded circuit can be readily replaced. Type ML-PL123 MICON Long Limiter Assembly for Paper Insulated Cable* Ordering Information Catalog Number Cable Size Recommended MICON Outlet Connection Indents in Cable Socket Dimensions in inches Cable Receptacle Compression Sleeve D L O.D. ML21-PL123 4/0 STR MA-21 C21-21 1 Diameter over cable insulation to be specified on order 9 7/8 1 7/8 ML25-PL123 250 MCM MA-25 C25-25 1 9 7/8 1 7/8 ML30-PL123 300 MCM MA-30 C30-30 2 10 3/8 2 3/16 ML35-PL123 350 MCM MA-40 C40-35 2 10 3/8 2 3/16 ML40-PL123 400 MCM MA-40 C40-40 2 10 3/8 2 3/16 ML50-PL123 500 MCM MA-50 C50-50 2 11 3/4 2 3/8 ML75-PL123 750 MCM MA-50-88 C50-50 2 12 1/4 2 9/16 * Closed end of sockets are sealed to make sockets oil tight Elements Type No. Name ML-1 1 Insulating Sleeve ML-PL2 2 Shell ML-PL3 3 Long Limiter L D 1 2 3 O D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
32 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00108, Revision 2, 11.5.2025 Specifications are subject to change without notice. 32 Network Underground The MICON limiter is designed to provide a fusible connecting point to the MICON outlet. The fusible section is made to close tolerances to ensure consistent conformity with the fusing time-current curves. The limiter will clear on severe loads or faults but will not clear on system overloads of short period. Types ML-R3, ML-P3 MICON Limiter for Use with MICON Limiter Assembly Types ML-R123 and ML-P123 L B A Ordering Information Catalog Number Cable Size Indents in Cable Socket Dimensions in inches For Rubber Insulated Cable For Paper* Insulated Cable A** B L ML21-R3 ML21-P3 4/0 STR 1 11/16 1 7/8 6 1/8 ML25-R3 ML25-P3 250 MCM 1 3/4 1 7/8 6 1/8 ML30-R3 ML30-P3 300 MCM 2 13/16 2 6 5/8 ML35-R3 ML35-P3 350 MCM 2 7/8 2 7 ML40-R3 ML40-P3 400 MCM 2 31/32 2 1/8 7 ML50-R3 ML50-P3 500 MCM 2 1 1/16 2 3/4 8 1/8 ML75-R3 ML75-P3 750 MCM 2 1 5/16 2 3/4 9 1/8 * Closed end of sockets are sealed to make sockets oil tight ** Diameter AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
33 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00112, Revision 2, 11.25.2025 Specifications are subject to change without notice. 33 Network Underground The MICON long limiter, for oil filled paper insulated cable, is designed to provide a fusible connecting point to the MICON outlet. The fusible section is made to close tolerances to insure consistent conformity with the fusing time-current curves. The limiter will clear on severe loads or faults but will not clear on system overloads of short period. Type ML-PL3 MICON Long Limiter for Paper Insulated Cable* for Use with MICON Long Limiter Assembly Type ML-PL123 Ordering Information Catalog Number Cable Size Indents in Cable Socket Dimensions in inches A** B L ML21-PL3 4/0 STR 1 11/16 3 7 1/4 ML25-PL3 250 MCM 1 3/4 3 1/8 7 1/4 ML30-PL3 300 MCM 2 13/16 3 1/2 8 ML35-PL3 350 MCM 2 7/8 3 1/2 8 3/8 ML40-PL3 400 MCM 2 31/32 3 1/2 8 3/8 ML50-PL3 500 MCM 2 1 1/16 4 1/4 9 9/16 ML75-PL3 750 MCM 2 1 5/16 4 1/4 10 7/16 L A B * Closed end of sockets are sealed to make sockets oil tight ** Diameter AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
34 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00144, Revision 3, 11.25.2025 Specifications are subject to change without notice. 34 Network Underground A composition molded shell consisting of two symmetrical halves with interlocking fingers. Internal cavities and heat confining barriers permit fusible section of MICON limiter to clear circuit without damage to surrounding insulation. Two shells constitute a pair as illustrated and defined by pairs in catalog numbers. Shells may be ordered independently by pairs for replacement. Types ML-R2, ML-P2 Limiter Shell for Use with MICON Limiter Assembly Types ML-R123, ML-P123, and ML-PL123 L A Ordering Information Catalog Number Cable Range Dimensions in inches For Rubber Insulated Cable For Paper* Insulated Cable L A** ML21-R2 ML21-P2 4/0 STR 5 15/32 1 17/32 ML25-R2 ML25-P2 250 MCM 5 15/32 1 17/32 ML30-R2 ML40-P2 300-400 MCM 5 15/16 1 21/32 ML40-R2 ML40-P2 300-400 MCM 5 15/16 1 21/32 ML50-R2 ML50-P2 500 MCM 7 1/16 1 13/16 ML75-R2 ML75-P2 750 MCM 7 5/16 2 3/32 * For use with regular or long MICON limiter types ML-P3 and ML-PL3 ** Diameter AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
35 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00110, Revision 2, 11.25.2025 Specifications are subject to change without notice. 35 Network Underground A two piece MYPAR sleeve for insulating the MICON limiter and shell assembly. The sleeve is designed to establish a snug fit on the MICON outlet and cable insulation reducing the operation of taping to a minimum. Type ML-1 MICON Limiter Insulating Sleeve for Use with MICON Limiter Assembly Types ML-R123, ML-P123, and ML-PL123 Ordering Information Catalog Number Cable Range Diameter Over Cable Insulation (I.D.) Dimensions in inches L O.D. ML25-1 4/0 STR - 250 MCM Diameter over cable insulation to be specified on order 9 3/4 1 29/32 ML40-1 300-400 MCM 10 3/8 2 7/32 ML50-1 500 MCM 11 3/4 2 21/32 ML75-1 750 MCM 12 1/4 2 5/8 L O D I D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
36 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00139, Revision 2, 11.25.2025 Specifications are subject to change without notice. 36 Network Underground A limiter tap for making tap connections from a continuous or cable ring bus in a transformer vault or manhole junction. Available for use with rubber or oil-filled paper insulated cable. The run section insulating cover and limiter insulating sleeve can be furnished on a number of sizes to offer complete molded insulation and reduce taping to a minimum. Information on the availability of complete or partial insulation will be readily furnished upon request. Types BCLA-R123, BCLA-P123, and BCLA-PL123 Limiter Tap Assembly for Rubber or Paper Insulated Cable Type Description Assembly Type Number Application BCLA-R123 For use with rubber insulated cable BCLA-P123 For use with paper insulated cable – furnished with regular length compression socket, but with closed end of socket sealed to make it oil tight BCLA-PL123 For use with paper insulated cable – furnished with long length compression socket, but with closed end of socket sealed to make it oil tight RUN CLAMP LIMITER SHELL COMPRESSION SOCKET RUN CLAMP INSULATING COVER LIMITER INSULATING SLEEVE Ordering Information Catalog Number Description Type Equivalent BCLA-1H Run clamp insulating cover - BCLA-1S Limiter insulating sleeve LLA-2P1 BCLA-2 Shell LLA-2P2 BCLA-3M Run clamp - BCLA-3F Limiter LLA-2R3 LLA-2P3 LLA-2PL3 AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
37 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00122, Revision 2, 11.25.2025 Specifications are subject to change without notice. 37 Network Underground The renewable MICON limiter link assembly is designed to establish a fusible connection to a MICON unit. The renewable link offers a quick and inexpensive means of re-energizing a cleared circuit. The renewable link also provides the possibility of regulating the circuit protection to various levels of current by choice of link ampere capacity. Type RLB-E Renewable MICON Limiter Link Assembly Ordering Information Catalog Number Cable Size Recommended for Use with RLB-E Indents in Cable Socket Dimensions in inches Renewable Limiter Link Furnished* Cable Receptacle Compression Sleeve D L Catalog Number Amp. Capacity RLB2-E 6 STR MA-21 C21-21 1 Diameter over cable insulation to be specified on order 15 1/2 F50 50 RLB4-E 4 STR MA-21 C21-21 1 15 1/2 F75 75 RLB6-E 2 STR MA-21 C21-21 1 15 1/2 F100 100 RLB8-E 1 STR MA-21 C21-21 1 15 1/2 F100 100 RLB10-E 1/0 STR MA-21 C21-21 1 15 1/2 F150 150 RLB13-E 2/0 STR MA-21 C21-21 1 15 1/2 F150 150 RLB17-E 3/0 STR MA-21 C21-21 1 15 1/2 F200 200 RLB21-E 4/0 STR MA-21 C21-21 1 15 1/2 F250 250 RLB25-E 250 MCM MA-25 C25-25 1 15 1/2 F250 250 RLB30-E 300 MCM MA-30 C30-30 2 15 1/2 F300 300 RLB35-E 350 MCM MA-40 C40-35 2 15 1/2 F300 300 RLB40-E 400 MCM MA-40 C40-40 2 15 1/2 F400 400 RLB50-E 500 MCM MA-50 C50-50 2 15 1/2 F400 400 * Minimum clearing current of furnished limiter is approximately NEC rubber insulated cable rating X2 Elements Type No. Name RLM-1 1 Insulating sleeve RLM-2 2 Insulating brushing RLM-3 3 Insulating adaptor RLM-50B 4 Mounting block F 5 Limiter link RL-2 6 Compression Terminal RLB-2 7 Micon Terminal L 3 7 4 CABLE RECEPTACLE MA TYPE 5 1 6 2 AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
38 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00128, Revision 2, 11.25.2025 Specifications are subject to change without notice. 38 Network Underground AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials A high impact, heat resistant, fiber reinforced phenolic resin base insulating mounting block. Designed to serve as a junction for connecting lugs or terminal adapters to limiter renewable link type F. Mounting studs are solidly anchored in block during molding process. The block may be ordered separately for replacement or other applications. Type RLM-B Limiter Mounting Block for Use with Renewable Limiter Link Assembly Types RLM-E and RLB-E Ordering Information Catalog Number RLM50-B 1 1 / 16 3/8 - 16 1 59 / 64 6 3 / 16 3 1 / 16 1 1 / 16 1 51 / 64
39 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00120, Revision 2, 11.15.2025 Specifications are subject to change without notice. 39 Network Underground A compression terminal designed to fit terminal ends of type RLM-B limiter mounting block. Closed end of lug is sealed to permit interchangeable use with rubber insulated or oil filled paper insulated cables. To insure high resistance to corrosion terminal is completely tin coated. Type RL-2 Compression Terminal for Use with Type RLM-B Limiter Mounting Block Ordering Information Catalog Number Cable Size Dimensions in inches Number of Indents Index Number A B O.D. L T RL2-2 6 STR 1 1 1/8 5/16 3 3/4 7/32 1 7 RL4-2 4 STR 1 1 1/8 11/32 3 3/4 7/32 1 8 RL6-2 2 STR 1 1 1/4 13/32 3 15/16 7/32 1 10 RL8-2 1 STR 1 1 3/8 15/32 4 1/16 7/32 1 11 RL10-2 1/0 STR 1 1 3/8 17/32 4 1/16 7/32 1 12 RL13-2 2/0 STR 13/16 1 1/2 9/16 3 13/16 1/8 1 13 RL17-2 3/0 STR 29/32 1 1/2 5/8 3 7/8 9/64 1 14 RL21-2 4/0 STR 1 1 5/8 11/16 4 1/16 9/64 1 15 RL25-2 250 MCM 1 1/8 1 5/8 3/4 4 1/8 5/32 1 16 RL30-2 300 MCM 1 3/16 2 13/16 4 1/2 5/32 2 17 RL35-2 350 MCM 1 9/32 2 7/8 4 9/16 11/64 2 18 RL40-2 400 MCM 1 3/8 2 1/8 31/32 4 3/4 3/16 2 19 RL50-2 500 MCM 1 17/32 2 1/4 1 1/16 4 7/8 7/32 2 20 O D L B T 2 1 / 16 1 1 / 16 7 / 16 A AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
40 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00129, Revision 2, 11.25.2025 Specifications are subject to change without notice. 40 Network Underground An insulating renewable limiter link assembly which serves as both a fuse and coupler. The renewable link offers a quick and inexpensive means of re-energizing cleared circuits. The renewable link also provides the possibility of regulating the circuit protection to various levels of current by choice of link ampere capacity. Type RLM-E Renewable Limiter Link Assembly Ordering Information Catalog Number Cable Size No. of Indents Dia. Over Cable Insulation D L in inches Renewable Limiter Link Furnished* Catalog Number Amp. Capacity RLM2-E 6 STR 1 Diameter over cable insulation to be specified on order 16 3/8 F50 50 RLM4-E 4 STR 1 16 3/8 F75 75 RLM6-E 2 STR 1 16 3/8 F100 100 RLM8-E 1 STR 1 16 3/8 F100 100 RLM10-E 1/0 STR 1 16 3/8 F150 150 RLM13-E 2/0 STR 1 16 3/8 F150 150 RLM17-E 3/0 STR 1 16 3/8 F200 200 RLM21-E 4/0 STR 1 16 3/8 F250 250 RLM25-E 250 MCM 1 16 3/8 F250 250 RLM30-E 300 MCM 2 16 3/8 F300 300 RLM35-E 350 MCM 2 16 3/8 F300 300 RLM40-E 400 MCM 2 16 3/8 F400 400 RLM50-E 500 MCM 2 16 3/8 F400 400 * Minimum clearing current of furnished limiter is approximately NEC rubber insulated cable rating X2 Elements Type No. Name RLM-1 1 Limiter Insulating Sleeve RLM-2 2 Limiter Insulating Bushing RLM-50B 3 Limiter Mounting Block F 4 Limiter Renewable Link RL-2 5 Compression Terminal L 3 4 5 1 2 D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
41 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00124, Revision 2, 11.25.2025 Specifications are subject to change without notice. 41 Network Underground A renewable type limiter link coupler for connecting rubber or paper insulated cables on end and providing a fusible element for cable protection. The cables are securely terminated at each end by a compression connector provided with a tapered sleeve and compression nut; the combination of which establishes high mechanical advantage and electrical efficiency. The fusible links are readily replaced after clearing a faulted line. Circuit protection can be established at various current levels by choice of link ampere capacity. Type RLL-E Renewable Limiter Link Coupler Ordering Information Catalog Number RLL-E Elements Type No. Name 1 Insulating Sleeve 2 Insulating Bushing 3 Limiter Mounting Block 4 Limiter Renewable Link 5 Socket Terminal L 3 4 5 1 2 AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
42 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00121, Revision 2, 11.26.2025 Specifications are subject to change without notice. 42 Network Underground A renewable MICON Limiter connector for making a fusible connection to an outlet of a MICON. Can be used for either rubber or paper insulated cable. The fusible assembly is connected to the MICON through use of the MICON terminal (3) and a standard cable receptacle, type MA (not furnished with assembly unless specified). Type RLBC-E Renewable Limiter Link Connector Ordering Information Catalog Number RLBC-E Elements Type No. Name 1 Insulating Sleeve 2 Insulating Bushing 3 Insulating Adapter 4 Limiter Mounting Block 5 Limiter Renewable Link 6 Socket Terminal 7 MICON Terminal 3 4 5 1 2 7 6 CABLE RECEPTACLE MA TYPE AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
43 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00123, Revision 2, 11.26.2025 Specifications are subject to change without notice. 43 Network Underground For making fusible connections to a flat bar bus or contact pad. Terminal pad can be furnished to any specified drilling and set at any desired angle. Limiter link is supplied as a unit with the fusible link housed in a shell to confine the arc established when link fuses. Type RLLA-E Special Renewable Link Connector for Rubber Oil-Filled, Paper Insulated Cable Ordering Information Catalog Number RLLA-E Elements Type No. Name 1 Insulating Sleeve 2 Insulating Bushing 3 Limiter Mounting Block 4 Limiter Renewable Link 5 Compression Terminal 6 Terminal 3 4 5 1 2 L 6 D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
44 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00113, Revision 2, 11.26.2025 Specifications are subject to change without notice. 44 Network Underground For providing a fusible tap connection to a continuous or ring bus. The renewable link can be readily replaced on cleared connectors. Type NCLA-E Straight Tap Connector Ordering Information Catalog Number NCLA-E Elements Type No. Name 1 Insulating Sleeve 2 Insulating Bushing 3 Limiter Mounting Block 4 Limiter Renewable Link 5 Compression Terminal 6 Insulating Hood 7 Run Clamp 3 4 5 1 2 7 6 AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
45 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00140, Revision 2, 11.26.2025 Specifications are subject to change without notice. 45 Network Underground An insulating cap to protect unused outlets on types CB10R and CB6R fusible crab connectors. The cap is slipped over unused outlets and held securely in position with several turns of rubber tape. Types CRC and CRC-C Insulating Caps Ordering Information Catalog Number Application Dimensions in inches I.D. O.D. L CRC-21 On 4/0 Tubing Outlet 2 7/64 2 15/32 4 3/16 CRC-50 On 500 MCM Tubing Outlet 2 5/32 2 33/64 4 9/16 CRC-50C On 500 MCM Cable Outlet 27/32 1 1/4 2 3/8 L O D I D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
46 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00081, Revision 2, 11.26.2025 Specifications are subject to change without notice. 46 Network Underground A thermal insulating wedge which is placed over the compressed tubular sections of outlets on types CB10R and CB6R fusible crab connectors. The wedges provide a thermal insulating protection from heat generated by fusible sections for the rubber taping which is wound from the cable insulation over the tubular outlet to the molded insulation of the connector. Type CRW Thermal Insulating Wedge Ordering Information Catalog Number Application Dimensions in inches I..D. D L CRW-21 On 4/0 Tubing Outlet 3/4 2 1/8 2 3/4 CRW-50 On 500 MCM Tubing Outlet 1 1/8 2 3/16 3 L D I D AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
47 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00083, Revision 2, 11.26.205 Specifications are subject to change without notice. 47 Network Underground A seamless sleeve coupler for splicing two cables end to end. This coupler is designed to fit the assembling dies of all standard hydraulic presses. Installation is quickly effected by slipping the connector over the free cable ends and forming indentations. Made of a pure high conductivity copper and tin coated. This style also available with an internal barrier for oil seal connections. Catalog Number: DPCP Type DPC Compression Coupler Ordering Information Catalog Number Cable Size D No. of Indents per Cable Dimensions in inches B L DPC-1 8 STR 1 1/2 1 1/16 DPC-2 6 STR 1 1 1/8 2 5/16 DPC-4 4 STR 1 1 1/8 2 5/16 DPC-5 3 STR 1 1 1/4 2 5/8 DPC-6 2 STR 1 1 1/4 2 5/8 DPC-8 1 STR 1 1 7/16 3 DPC-10 1/0 STR 1 1 7/16 3 DPC-13 2/0 STR 1 1 1/2 3 1/8 DPC-17 3/0 STR 1 1 1/2 3 1/8 DPC-21 4/0 STR 1 1 5/8 3 3/8 DPC-25 250 MCM 1 1 5/8 3 3/8 DPC-30 300 MCM 2 2 1/16 4 1/4 DPC-35 350 MCM 2 2 1/16 4 1/4 DPC-40 400 MCM 2 2 1/8 4 3/8 DPC-50 500 MCM 2 2 1/4 4 5/8 DPC-55 550 MCM 2 2 5/8 5 3/8 DPC-60 600 MCM 2 2 11/16 5 1/2 DPC-65 650 MCM 2 2 13/16 5 3/4 DPC-75 750 MCM 2 2 7/8 5 7/8 DPC-80 800 MCM 2 2 15/16 6 DPC-85 850 MCM 2 2 15/16 6 DPC-100 1000 MCM 2 3 6 1/8 DPC-125 1250 MCM 2 3 1/4 6 5/8 DPC-130 1300 MCM 2 3 1/4 6 5/8 DPC-150 1500 MCM 2 3 1/4 6 5/8 DPC-175 1750 MCM 2 3 1/2 7 1/8 DPC-200 2000 MCM 2 3 1/2 7 1/8 B L B AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
48 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00085, Revision 2, 11.26.2025 Specifications are subject to change without notice. 48 Network Underground A seamless sleeve reducing coupler for splicing two cables end to end. Compression indents can be made with all standard compression tools. Made of pure high conductivity copper tin coated. Type DPR Compression Reducing Coupler Ordering Information Catalog Number Cable Size D No. of Indents per Cable Dimensions in inches C D DPR4-2 #4-#6 1-1 1 1/8 1 1/8 DPR6-2 #2-#6 1-1 1 1/4 1 1/8 DPR6-4 #2-#4 1-1 1 1/4 1 1/8 DPR10-2 1/0-#6 1-1 1 3/8 1 1/8 DPR10-4 1/0-#4 1-1 1 3/8 1 1/8 DPR10-6 1/0-#6 1-1 1 3/8 1 1/4 DPR13-2 2/0-#6 1-1 1 1/2 1 1/8 DPR13-4 2/0-#4 1-1 1 1/2 1 1/8 DPR13-6 2/0-#2 1-1 1 1/2 1 1/4 DPR13-10 2/0-1/0 1-1 1 1/2 1 3/8 DPR21-2 4/0-#6 1-1 1 5/8 1 1/8 DPR21-4 4/0-#4 1-1 1 5/8 1 1/8 DPR21-6 4/0-#2 1-1 1 5/8 1 1/4 DPR21-10 4/0-1/0 1-1 1 5/8 1 3/8 DPR21-13 4/0-2/0 1-1 1 5/8 1 1/2 DPR25-4 250-#4 1-1 1 5/8 1 1/8 DPR25-6 250-#2 1-1 1 5/8 1 1/4 DPR25-10 250-1/0 1-1 1 5/8 1 3/8 DPR25-13 250-2/0 1-1 1 5/8 1 1/2 DPR25-21 250-4/0 1-1 1 5/8 1 5/8 DPR35-6 350-#2 2-1 2 1 1/4 DPR35-10 350-1/0 2-1 2 1 3/8 DPR35-13 350-2/0 2-1 2 1 1/2 C D Catalog Number Cable Size D No. of Indents per Cable Dimensions in inches C D DPR35-21 350-4/0 2-1 2 1 5/8 DPR35-25 350-250 2-1 2 1 5/8 DPR50-10 500-1/0 2-1 2 1/4 1 3/8 DPR50-13 500-2/0 2-1 2 1/4 1 1/2 DPR50-21 500-4/0 2-1 2 1/4 1 5/8 DPR50-25 500-210 2-1 2 1/4 1 5/8 DPR50-35 500-350 2-2 2 1/4 2 DPR75-13 750-2/0 2-1 2 7/8 1 1/2 DPR75-21 750-4/0 2-1 2 7/8 1 5/8 DPR75-25 750-250 2-1 2 7/8 1 5/8 DPR75-35 750-350 2-1 2 7/8 2 DPR75-50 750-500 2-2 2 7/8 2 1/4 DPR100-21 1000-4/0 2-1 3 1 5/8 DPR100-25 1000-250 2-1 3 1 5/8 DPR100-35 1000-350 2-2 3 2 DPR100-50 1000-500 2-2 3 2 1/4 DPR100-75 1000-750 2-2 3 2 7/8 DPR150-25 1500-250 2-1 3 1/4 1 5/8 DPR150-35 1500-350 2-2 3 1/4 2 DPR150-50 1500-500 2-2 3 1/4 2 1/4 DPR150-75 1500-750 2-1 3 1/4 2 7/8 DPR150-100 1500-1000 2-2 3 1/4 3 AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
49 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00080, Revision 1, 2.18.2022 Specifications are subject to change without notice. 49 Network Underground A tee coupler for joining two cables o the run and taking off a right angle tap at the junction. Made of high conductivity copper and completely tin plated. The round run and tap sections make for an easy and neat taping job. Other sizes than those listed can be readily furnished upon request. Type CRT Compression Tee Coupler Ordering Information Catalog Number Cable Size No. of Indents B/B1 Dimensions in inches Run D Tap D1 B B1 C* L W CTR10-2 1/0 STR 6 STR 1/1 1 7/16 1 1/8 17/32 3 11/16 2 CTR10-4 1/0 STR 4 STR 1/1 1 7/16 1 1/8 17/32 3 3/4 2 CTR10-6 1/0 STR 2 STR 1/1 1 7/16 1 1/4 17/32 3 13/16 2 1/8 CTR10-8 1/0 STR 1 STR 1/1 1 7/16 1 7/16 17/32 3 7/8 2 1/4 CTR10-10 1/0 STR 1/0 STR 1/1 1 7/16 1 7/16 17/32 3 7/8 2 1/4 CTR13-2 2/0 STR 6 STR 1/1 1 1/2 1 1/8 9/16 3 11/16 2 CTR13-4 2/0 STR 4 STR 1/1 1 1/2 1 1/8 9/16 3 3/4 2 CTR13-6 2/0 STR 2 STR 1/1 1 1/2 1 1/4 9/16 3 13/16 2 1/8 CTR13-8 2/0 STR 1 STR 1/1 1 1/2 1 7/16 9/16 3 7/8 2 1/4 CTR13-10 2/0 STR 1/0 STR 1/1 1 1/2 1 7/16 9/16 3 7/8 2 1/4 CTR13-13 2/0 STR 2/0 STR 1/1 1 1/2 1 1/2 9/16 3 15/16 2 5/16 CTR21-4 4/0 STR 4 STR 1/1 1 5/8 1 1/8 11/16 3 15/16 2 1/8 CTR21-6 4/0 STR 2 STR 1/1 1 5/8 1 1/4 11/16 4 1/16 2 1/4 CTR21-8 4/0 STR 1 STR 1/1 1 5/8 1 7/16 11/16 4 1/16 2 3/8 CTR21-10 4/0 STR 1/0 STR 1/1 1 5/8 1 7/16 11/16 4 1/8 2 3/8 CTR21-13 4/0 STR 2/0 STR 1/1 1 5/8 1 1/2 11/16 4 3/16 2 7/16 CTR21-21 4/0 STR 4/0 STR 1/1 1 5/8 1 5/8 11/16 4 1/4 2 1/2 CTR25-4 250 MCM 4 STR 1/1 1 5/8 1 1/8 3/4 3 7/8 2 1/4 CTR25-6 250 MCM 2 STR 1/1 1 5/8 1 1/4 3/4 4 2 3/8 CTR25-8 250 MCM 1 STR 1/1 1 5/8 1 7/16 3/4 4 2 7/16 CTR25-10 250 MCM 1/0 STR 1/1 1 5/8 1 7/16 3/4 4 1/16 2 7/16 CTR25-13 250 MCM 2/0 STR 1/1 1 5/8 1 1/2 3/4 4 1/8 2 1/2 C B1 L W B B AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials * Diameter over run barrel
50 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00080, Revision 1, 2.18.2022 Specifications are subject to change without notice. 50 Network Underground Type CRT Compression Tee Coupler Catalog Number Cable Size No. of Indents B/B1 Dimensions in inches Run D Tap D1 B B1 C* L W CTR25-21 250 MCM 4/0 STR 1/1 1 5/8 1 5/8 3/4 4 3/16 2 9/16 CTR25-25 250 MCM 250 MCM 1/1 1 5/8 1 5/8 3/4 4 1/4 2 9/16 CTR30-6 300 MCM 2 STR 2-1 2 1/16 1 1/4 13/16 5 3/16 2 3/8 CTR30-8 300 MCM 1 STR 2-1 2 1/16 1 7/16 13/16 5 5/16 2 7/16 CTR30-10 300 MCM 1/0 STR 2-1 2 1/16 1 7/16 13/16 5 5/16 2 7/16 CTR30-13 300 MCM 2/0 STR 2-1 2 1/16 1 1/2 13/16 5 5/16 2 1/2 CTR30-21 300 MCM 4/0 STR 2-1 2 1/16 1 5/8 13/16 5 7/16 2 9/16 CTR30-25 300 MCM 250 MCM 2-1 2 1/16 1 5/8 13/16 5 1/2 2 9/16 CTR30-30 300 MCM 300 MCM 2-2 2 1/16 2 1/16 13/16 5 9/16 3 1/8 CTR35-6 350 MCM 2 STR 2-1 2 1/16 1 1/4 7/8 5 3/16 2 7/16 CTR35-8 350 MCM 1 STR 2-1 2 1/16 1 7/16 7/8 5 5/16 2 5/8 CTR35-10 350 MCM 1/0 STR 2-1 2 1/16 1 7/16 7/8 5 5/16 2 9/16 CTR35-13 350 MCM 2/0 STR 2-1 2 1/16 1 1/2 7/8 5 5/16 2 9/16 CTR35-21 350 MCM 4/0 STR 2-1 2 1/16 1 5/8 7/8 5 7/16 2 5/8 CTR35-25 350 MCM 250 MCM 2-1 2 1/16 1 5/8 7/8 5 1/2 2 5/8 CTR35-30 350 MCM 300 MCM 2-2 2 1/16 2 1/16 7/8 5 9/16 3 1/4 CTR35-35 350 MCM 350 MCM 2-2 2 1/16 2 1/16 7/8 5 5/8 3 1/4 CTR40-10 400 MCM 1/0 STR 2-1 2 1/8 1 7/16 31/32 5 5/16 2 5/8 CTR40-13 400 MCM 2/0 STR 2-1 2 1/8 1 1/2 31/32 5 5/16 2 5/8 CTR40-21 400 MCM 4/0 STR 2-1 2 1/8 1 5/8 31/32 5 7/16 2 11/16 CTR40-25 400 MCM 250 MCM 2-1 2 1/8 1 5/8 31/32 5 1/2 2 11/16 CTR40-30 400 MCM 300 MCM 2-2 2 1/8 2 1/16 31/32 5 9/16 3 3/16 CTR40-35 400 MCM 350 MCM 2-2 2 1/8 2 1/16 31/32 5 5/8 3 3/16 CTR40-40 400 MCM 400 MCM 2-2 2 1/8 2 1/8 31/32 5 5/8 3 1/4 CTR50-10 500 MCM 1/0 STR 2-1 2 1/4 1 7/16 1 1/16 5 11/16 2 3/4 CTR50-13 500 MCM 2/0 STR 2-1 2 1/4 1 1/2 1 1/16 5 11/16 2 3/4 CTR50-21 500 MCM 4/0 STR 2-1 2 1/4 1 5/8 1 1/16 5 13/16 2 13/16 CTR50-25 500 MCM 250 MCM 2-1 2 1/4 1 5/8 1 1/16 5 7/8 2 13/16 CTR50-30 500 MCM 300 MCM 2-2 2 1/4 2 1/16 1 1/16 5 15/16 3 7/16 CTR50-35 500 MCM 350 MCM 2-2 2 1/4 2 1/16 1 1/16 6 3 7/16 CTR50-40 500 MCM 400 MCM 2-2 2 1/4 2 1/8 1 1/16 6 1/16 3 1/2 CTR50-50 500 MCM 500 MCM 2-2 2 1/4 2 1/4 1 1/16 6 3/16 3 5/8 * Diameter over run barrel
51 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00084, Revision 2, 11.26.2025 Specifications are subject to change without notice. 51 Network Underground A precision made compression terminal lug for a full range of conductor sizes with 1, 2, and 4 hole pads in the larger sizes. Made of tin coated pure copper with a minimum conductivity of 98% I.A.C.S. Conductor is secured by identifying the barrel with any standard compression tool made for electrical lugs. Type DPL Compression Terminal Lug Ordering Information Catalog Number Cable Size D Screw Size No. of Holes in Pad No. of Indents B/B1 Dimensions in inches A B C L T X Y & Z DPL1-1 #8 STR #10 1 1 11/32 7/16 1/2 1 1/8 5/64 7/32 - DPL2-1 #6 STR 1/4 1 1 11/32 1 1/8 1/2 1 13/16 3/32 1/4 - DPL2-2 #6 STR 1/4 2 1 11/32 1 1/8 1 3/16 2 1/2 3/32 1/4 5/8 DPL4-1 #4 STR 1/4 1 1 1/2 1 1/8 1/2 1 13/16 3/32 1/4 - DPL4-2 #4 STR 1/4 2 1 1/2 1 1/8 1 3/16 2 1/2 3/32 1/4 5/8 DPL5-1 #3 STR 5/16 1 1 17/32 1 1/4 3/4 2 1/4 3/32 3/8 - DPL5-2 #3 STR 5/16 2 1 17/32 1 1/4 1 1/2 2 15/16 3/32 11/32 3/4 DPL6-1 #2 STR 5/16 1 1 19/32 1 1/4 3/4 2 1/4 7/64 3/8 - DPL6-2 #2 STR 5/16 2 1 19/32 1 1/4 1 1/2 2 15/16 7/64 11/32 3/4 DPL8-1 #1 STR 5/16 1 1 11/16 1 3/8 3/4 2 3/8 7/64 3/8 - DPL8-2 #1 STR 5/16 2 1 11/16 1 3/8 1 5/8 3 1/4 7/64 11/32 7/8 DPL10-1 1/0 STR 5/16 1 1 3/4 1 3/8 3/4 2 11/16 1/8 3/8 - DPL10-2 1/0 STR 5/16 2 1 3/4 1 3/8 1 5/8 3 7/16 1/8 11/32 7/8 DPL13-1 2/0 STR 3/8 1 1 13/16 1 1/2 7/8 2 13/16 1/8 7/16 - DPL13-2 2/0 STR 5/16 2 1 13/16 1 1/2 1 5/8 3 5/8 1/8 11/32 7/8 DPL17-1 3/0 STR 1/2 1 1 29/32 1 1/2 1 3 1/8 1/2 - DPL17-2 3/0 STR 3/8 2 1 29/32 1 1/2 1 13/16 3 13/16 1/8 3/8 1 DPL21-1 4/0 STR 1/2 1 1 1 1 5/8 1 3 3/16 9/64 1/2 - DPL21-2 4/0 STR 3/8 2 1 1 1 5/8 1 13/16 3 15/16 9/64 3/8 1 DPL25-1 250 MCM 1/2 1 1 1 3/32 1 5/8 1 1/8 3 9/16 5/32 9/16 - DPL25-2 250 MCM 3/8 2 1 1 3/32 1 5/8 1 7/8 4 5/16 5/32 3/8 1 1/16 DPL30-1 300 MCM 1/2 1 2 1 3/16 2 1 1/8 3 9/16 5/32 9/16 - DPL30-2 300 MCM 3/8 2 2 1 3/16 2 1 7/8 4 5/16 5/32 3/8 1 1/16 DPL35-1 350 MCM 1/2 1 2 1 9/32 2 1 1/8 3 9/16 3/16 9/16 - DPL35-2 350 MCM 3/8 2 2 1 9/32 2 1 7/8 4 5/16 3/16 3/8 1 1/16 C L Y X A B T Y X A Z A AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
52 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00084, Revision 2, 11.26.2025 Specifications are subject to change without notice. 52 Network Underground Type DPL Compression Terminal Lug Catalog Number Cable Size D Screw Size No. of Holes in Pad No. of Indents B/B1 Dimensions in inches A B C L T X Y & Z DPL40-1 400 MCM 5/8 1 2 1 13/32 2 1/8 1 1/2 4 1/4 3/16 3/4 - DPL40-2 400 MCM 3/8 2 2 1 13/32 2 1/8 2 4 3/4 3/16 7/16 1 1/16 DPL 50-1 500 MCM 5/8 1 2 1 17/32 2 1/4 1 1/2 4 3/8 1/4 3/4 - DPL 50-2 500 MCM 3/8 2 2 1 17/32 2 1/4 2 4 7/8 1/4 7/16 1 1/16 DPL 55-1 550 MCM 5/8 1 2 1 5/8 2 5/8 1 5/8 4 15/16 1/4 13/16 - DPL 55-2 550 MCM 3/8 2 2 1 5/8 2 5/8 2 1/16 5 3/8 1/4 7/16 1 1/8 DPL 60-1 600 MCM 5/8 1 2 1 3/4 2 11/16 1 3/4 5 1/8 9/32 7/8 - DPL 60-2 600 MCM 3/8 2 2 1 3/4 2 11/16 2 1/16 5 7/16 9/32 7/16 1 1/8 DPL 65-1 650 MCM 5/8 1 2 1 25/32 2 13/16 1 3/4 5 5/16 9/32 7/8 - DPL 65-2 650 MCM 3/8 2 2 1 25/32 2 13/16 2 3/16 5 3/4 9/32 1/2 1 1/8 DPL 75-1 750 MCM 5/8 1 2 1 29/32 2 7/8 1 15/16 5 5/8 9/32 7/8 - DPL 75-2 750 MCM 3/8 2 2 1 29/32 2 7/8 2 3/16 5 7/8 9/32 1/2 1 1/8 DPL 80-1 800 MCM 5/8 1 2 1 31/32 2 15/16 1 15/16 5 11/16 5/16 15/16 - DPL 80-2 800 MCM 3/8 2 2 1 31/32 2 15/16 2 3/16 5 15/16 5/16 1/2 1 1/8 DPL 85-1 850 MCM 5/8 1 2 2 2 15/16 1 15/16 5 11/16 5/16 15/16 - DPL 85-2 850 MCM 3/8 2 2 2 2 15/16 2 3/16 5 15/16 5/16 1/2 1 1/8 DPL 85-2-S50 850 MCM 1/2 2 2 2 2 15/16 3 6 3/4 5/16 5/8 1 3/4 DPL 100-1 1000 MCM 5/8 1 2 2 3/16 3 2 1/8 6 11/32 15/16 - DPL 100-2 1000 MCM 1/2 2 2 2 3/16 3 2 7/16 6 5/16 11/32 9/16 1 1/4 DPL 100-2-S50 1000 MCM 1/2 2 2 2 3/16 3 3 6 7/8 11/32 5/8 1 3/4 DPL 100-4 1000 MCM 3/8 4 2 2 3/16 3 2 3/16 6 1/16 11/32 1/2 1 1/8 DPL 125-1 1250 MCM 3/4 1 2 2 13/32 3 3/16 2 1/8 6 3/8 3/8 1 1/16 - DPL 125-2 1250 MCM 1/2 2 2 2 13/32 3 3/16 2 5/8 6 7/8 3/8 9/16 1 3/8 DPL 125-2-S50 1250 MCM 1/2 2 2 2 13/32 3 3/16 3 7 1/4 3/8 5/8 1 3/4 DPL 125-4 1250 MCM 1/2 4 2 2 13/32 3 3/16 2 5/8 6 7/8 3/8 9/16 1 3/8 DPL 130-1 1300 MCM 3/4 1 2 2 17/32 3 3/16 2 1/8 6 1/2 13/32 1 1/16 - DPL 130-2 1300 MCM 1/2 2 2 2 17/32 3 3/16 2 5/8 7 13/32 9/16 1 3/8 DPL 130-2-S50 1300 MCM 1/2 2 2 2 17/32 3 3/16 3 7 3/8 13/32 5/8 1 3/4 DPL 150-1 1500 MCM 3/4 1 2 2 11/16 3 3/16 2 5/8 6 11/16 13/32 1 1/8 - DPL 150-2 1500 MCM 1/2 2 2 2 11/16 3 3/16 2 1/4 7 1/16 13/32 9/16 1 3/8 DPL 150-2-S50 1500 MCM 1/2 2 2 2 11/16 3 3/16 3 7 1/16 13/32 5/8 1 3/4 DPL 150-4 1500 MCM 1/2 4 2 2 11/16 3 3/16 2 5/8 7 1/16 13/32 9/16 1 3/8 DPL 175-1 1750 MCM 3/4 1 2 2 7/8 3 7/16 2 1/4 7 1/4 7/16 1 1/8 - DPL 175-2 1750 MCM 1/2 2 2 2 7/8 3 7/16 2 3/4 7 3/4 7/16 9/16 1 1/2 DPL 175-2-S50 1750 MCM 1/2 2 2 2 7/8 3 7/16 3 8 7/16 5/8 1 3/4 DPL 175-4 1750 MCM 1/2 4 2 2 7/8 3 7/16 2 3/4 7 3/4 7/16 9/16 1 1/2 DPL 200-1 2000 MCM 3/4 1 2 3 3/32 3 7/16 2 3/8 7 7/16 15/32 13/16 - DPL 200-2 2000 MCM 1/2 2 2 3 3/32 3 7/16 2 3/4 7 13/16 15/32 9/16 1 1/2 DPL 200-2-S50 2000 MCM 1/2 2 2 3 3/32 3 7/16 3 8 1/16 15/32 5/8 1 3/4 DPL 200-4 2000 MCM 1/2 4 2 3 3/32 3 7/16 2 3/4 7 13/16 15/32 9/16 1 1/2
53 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00071, Revision 3, 11.26.2025 Specifications are subject to change without notice. 53 Network Underground A tee connector composed of a clamp type run element and a compression type connector for the tap. This connector has a wide application where various taps are to be taken from a continuous run. To ensure high resistance to corrosion connector is completely tin coated. Bolts, also tin plated are made of high strength silicon bronze. Other sizes than those shown below can be readily furnished. Type BCKT Tee Connector B L H FIG. 1 FIG. 2 Ordering Information Catalog No. Conductor Size Fig. No. Dimensions in inches Run Tap B H L Bolt Size BCKT21-6 4/0 STR 2 STR 1 1 25 1 25 3 63 3/8 BCKT21-10 4/0 STR 1/0 STR 1 1 25 1 25 3 75 3/8 BCKT21-13 4/0 STR 2/0 STR 1 1 25 1 27 3 88 3/8 BCKT21-21 4/0 STR 4/0 STR 2 2 00 1 34 4 38 3/8 BCKT25-6 250 MCM 2 STR 1 1 38 1 44 3 75 3/8 BCKT25-10 250 MCM 1/0 STR 1 1 38 1 4375 3 875 3/8 BCKT25-13 250 MCM 2/0 STR 1 1 38 1 4375 4 00 3/8 BCKT25-21 250 MCM 4/0 STR 2 2 00 1 50 4 50 3/8 BCKT25-25 250 MCM 250 MCM 2 2 00 1 625 4 70 3/8 BCKT35-10 350 MCM 1/0 STR 1 1 38 1 50 4 00 3/8 BCKT35-13 350 MCM 2/0 STR 1 1 38 1 50 4 125 3/8 BCKT35-21 350 MCM 4/0 STR 2 2 00 1 50 4 25 3/8 BCKT35-25 350 MCM 250 MCM 2 2 00 1 75 4 88 3/8 BCKT35-35 350 MCM 350 MCM 2 2 00 1 75 5 00 3/8 AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
54 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00071, Revision 3, 11.26.2025 Specifications are subject to change without notice. 54 Network Underground Type BCKT Tee Connector Ordering Information Catalog No. Conductor Size Fig. No. Dimensions in inches Run Tap B H L Bolt Size BCKT50-13 500 MCM 2/0 STR 1 1 25 1 66 4 00 3/8 BCKT50-21 500 MCM 4/0 STR 2 2 00 1 66 4 59 3/8 BCKT50-25 500 MCM 250 MCM 2 2 00 1 75 4 50 3/8 BCKT50-35 500 MCM 350 MCM 2 2 00 1 94 5 22 3/8 BCKT50-50 500 MCM 500 MCM 2 2 00 1 94 5 19 3/8 BCKT75-10 750 MCM 1/0 STR 1 1 38 1 94 4 63 3/8 BCKT75-13 750 MCM 2/0 STR 1 1 38 1 94 4 75 3/8 BCKT75-21 750 MCM 4/0 STR 2 2 00 2 00 5 00 3/8 BCKT75-25 750 MCM 250 MCM 2 2 00 2 00 4 50 3/8 BCKT75-35 750 MCM 350 MCM 2 2 00 2 00 5 38 3/8 BCKT75-50 750 MCM 500 MCM 2 2 00 2 00 5 63 3/8 BCKT75-75 750 MCM 750 MCM 2 2 00 2 25 5 63 3/8 BCKT100-13 1000 MCM 2/0 STR 1 1 50 2 13 4 81 3/8 BCKT100-21 1000 MCM 4/0 STR 2 2 00 2 22 5 00 3/8 BCKT100-25 1000 MCM 250 MCM 2 2 00 2 19 5 25 3/8 BCKT100-35 1000 MCM 350 MCM 2 2 00 2 19 5 44 3/8 BCKT100-50 1000 MCM 500 MCM 2 2 00 2 19 5 69 3/8 BCKT100-75 1000 MCM 750 MCM 2 2 00 2 19 6 41 3/8 BCKT100-100 1000 MCM 1000 MCM 2 2 63 2 50 7 00 1/2 BCKT150-21 1500 MCM 4/0 STR 2 2 00 2 50 5 31 3/8 BCKT150-25 1500 MCM 250 MCM 2 2 00 2 50 5 81 3/8 BCKT150-35 1500 MCM 350 MCM 2 2 00 2 50 6 19 3/8 BCKT150-50 1500 MCM 500 MCM 2 2 00 2 50 6 19 3/8 BCKT150-60 1500 MCM 600 MCM 2 2 00 2 50 6 81 3/8 BCKT150-75 1500 MCM 750 MCM 2 2 00 2 50 6 69 3/8 BCKT150-100 1500 MCM 1000 MCM 2 2 75 2 69 7 25 1/2 BCKT150-150 1500 MCM 1500 MCM 2 2 75 2 69 7 97 1/2 BCKT200-25 2000 MCM 250 MCM 2 2 00 2 50 5 63 3/8 BCKT200-35 2000 MCM 350 MCM 2 2 00 2 50 6 25 3/8 BCKT200-50 2000 MCM 500 MCM 2 2 00 2 50 6 25 3/8 BCKT200-75 2000 MCM 750 MCM 2 2 75 2 50 6 88 3/8 BCKT200-100 2000 MCM 1000 MCM 2 2 75 2 69 7 44 1/2 BCKT200-150 2000 MCM 1500 MCM 2 2 75 2 69 7 75 1/2 BCKT200-200 2000 MCM 2000 MCM 2 2 75 2 69 8 13 1/2
55 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00093, Revision 2, 12.5.2025 Specifications are subject to change without notice. 55 Network Underground A cast bronze tee connector whose tap element is provided with a cast hood which serves as a shroud over the insulation of the cable. This accomplishes a watertight weather seal on the tap cable when the body and shroud is taped to the insulation of the cable. The clamping element is a tapered sleeve and gland nut similar to type MA cable receptacles. When ordering specify kV rating and diameter over cable insulation. Type HNT Hood Nut Tee Connector Ordering Information Catalog Number* Cable Size Dimensions in inches Bolt Size Main Tap W L Approx. HNT21-6-X 4/0 #2 2 4 403 3/8 HNT21-10-X 4/0 1/0 2 4 403 3/8 HNT21-13-X 4/0 2/0 2 4 653 3/8 HNT21-21-X 4/0 4/0 2 4 653 3/8 HNT25-6-X 250 #2 2 4 450 3/8 HNT25-10-X 250 1/0 2 4 450 3/8 HNT25-13-X 250 2/0 2 4 450 3/8 HNT25-21-X 250 4/0 2 4 700 3/8 HNT25-25-X 250 250 2 4 700 3/8 HNT35-10-X 350 1/0 2 4 556 3/8 HNT35-13-X 350 2/0 2 4 556 3/8 HNT35-21-X 350 4/0 2 4 556 3/8 HNT35-25-X 350 250 2 4 806 3/8 HNT35-35-X 350 350 2 4 806 3/8 HNT50-13-X 500 2/0 2 5 289 3/8 HNT50-21-X 500 4/0 2 5 539 3/8 Catalog Number* Cable Size Dimensions in inches Bolt Size Main Tap W L Approx. HNT50-25-X 500 250 2 5 539 3/8 HNT50-35-X 500 350 2 5 539 3/8 HNT50-50-X 500 500 2 5 539 3/8 HNT75-13-X 750 2/0 2 5 623 3/8 HNT75-21-X 750 4/0 2 5 873 3/8 HNT75-25-X 750 250 2 5 873 3/8 HNT75-35-X 750 350 2 5 873 3/8 HNT75-50-X 750 500 2 5 873 3/8 HNT75-75-X 750 750 2 5 873 3/8 HNT100-13-X 1000 2/0 2 6 277 3/8 HNT100-21-X 1000 4/0 2 6 527 3/8 HNT100-25-X 1000 250 2 6 527 3/8 HNT100-35-X 1000 350 2 6 527 3/8 HNT100-50-X 1000 500 2 6 527 3/8 HNT100-75-X 1000 750 2 6 527 3/8 HNT100-100-X 1000 1000 2 6 902 3/8 L W MAIN TAP * X in the catalog number is to be replaced with the kV rating AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
56 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00131, Revision 2, 12.5.2025 Specifications are subject to change without notice. 56 Network Underground A cast bronze terminal with a cast hood serving as a shroud over the insulation of the cable. This provides a watertight weather seal on cable when the body and hood is taped to the insulation of the cable. The cable clamping element is a tapered sleeve and gland nut similar to type MA cable receptacles. When ordering specify kV rating and diameter over cable insulation. Type STLH Hood Nut Terminal Connector Ordering Information Catalog Number Cable Size Fig. No. Dimensions in inches A C G L X Y & Z H T STLH10-1 1/0 1 13/16 13/16 1/2 3 1/8 13/32 - 13/32 1/4 STLH10-2 1/0 2 13/16 1 7/8 1/2 4 3/16 7/16 1 13/32 1/4 STLH13-1 2/0 1 13/16 13/16 9/16 3 7/16 13/32 - 13/32 1/4 STLH13-2 2/0 2 13/16 1 7/8 9/16 4 1/2 7/16 1 13/32 1/4 STLH17-1 3/0 1 1 1 5/8 3 3/4 1/2 - 13/32 9/32 STLH17-2 3/0 2 1 1 7/8 5/8 4 5/8 7/16 1 13/32 9/32 STLH21-1 4/0 1 1 1 5/8 3 3/4 1/2 - 13/32 9/32 STLH21-2 4/0 2 1 1 7/8 5/8 4 5/8 7/16 1 13/32 9/32 STLH25-1 250 MCM 1 1 3/16 1 3/16 11/16 4 1/8 19/32 - 17/32 5/16 STLH25-2 250 MCM 2 1 3/16 1 7/8 11/16 5 7/16 1 13/32 5/16 STLH30-1 300 MCM 1 1 3/16 1 3/16 3/4 4 1/4 19/32 - 17/32 5/16 STLH30-2 300 MCM 2 1 3/16 1 7/8 3/4 5 1/8 7/16 1 13/32 5/16 STLH35-1 350 MCM 1 1 3/16 1 3/16 3/4 4 1/4 19/32 - 17/32 11/32 STLH35-2 350 MCM 2 1 3/16 1 7/8 3/4 5 1/8 7/16 1 13/32 11/32 STLH40-1 400 MCM 1 1 3/8 1 3/8 7/8 5 11/16 - 17/32 11/32 STLH40-2 400 MCM 2 1 7/8 1 7/8 7/8 5 1/2 7/16 1 13/32 11/32 Z X FIG. 1 FIG. 3 FIG. 2 L A C T G Y H H H A A C C X Y AFL’s Dossert ® product line offers a wide range of substation accessories in low voltage up to 765 kV applications in bronze or aluminum materials
57 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00131, Revision 2, 12.5.2025 Specifications are subject to change without notice. 57 Network Underground Type STLH Hood Nut Terminal Connector Ordering Information (cont.) Catalog Number Cable Size Fig. No. Dimensions in inches A C G L X Y & Z H T STLH50-1 500 MCM 1 1 3/8 1 3/8 7/8 5 1/4 11/16 - 17/32 3/8 STLH50-2 500 MCM 2 1 3/8 1 7/8 7/8 5 3/4 7/16 1 13/32 3/8 STLH50-4 500 MCM 3 2 2 7/8 5 7/8 1/2 1 13/32 3/8 STLH75-2 750 MCM 2 1 3/4 2 5/8 1 6 7/8 9/16 1 1/2 9/16 7/16 STLH75-4 750 MCM 3 2 2 1 6 1/4 1/2 1 13/32 7/16 STLH80-2 800 MCM 2 1 3/4 2 5/8 1 7 1/8 9/16 1 1/2 9/16 7/16 STLH80-4 800 MCM 3 2 2 1 6 1/2 1/2 1 13/32 7/16 STLH100-2 1000 MCM 2 2 3 1 1/8 7 7/8 9/16 1 1/2 9/16 15/32 STLH100-4 1000 MCM 3 3 3 1 1/8 7 7/8 3/4 1 1/2 9/16 15/32 STLH125-2 1250 MCM 2 2 1/4 2 5/8 1 3/16 7 1/2 9/16 1 1/2 9/16 1/2 STLH125-4 1250 MCM 3 3 3 1 3/16 7 7/8 3/4 1 1/2 9/16 1/2 STLH150-2 1500 MCM 2 2 1/2 3 1 1/4 8 1/4 5/8 1 3/4 9/16 9/16 STLH150-4 1500 MCM 3 3 3 1 1/4 8 1/4 3/4 1 1/2 9/16 9/16 STLH175-2 1750 MCM 2 2 1/2 3 1 1/2 8 1/2 5/8 1 3/4 9/16 5/8 STLH175-4 1750 MCM 3 3 3 1 1/2 8 1/2 3/4 1 1/2 9/16 5/8 STLH200-2 2000 MCM 2 2 3/4 3 1 5/8 8 7/8 5/8 1 3/4 9/16 5/8 STLH200-4 2000 MCM 3 3 3 1 5/8 8 7/8 3/4 1 1/2 9/16 5/8
58 AFLglobal.com 1 (800) 890-8878 © 2011, AFL, all rights reserved. PP-3-00079, Revision 2, 12.5.2025 Specifications are subject to change without notice. 58 Network Underground Alnox ® UG Electrical Joint Compound Alnox UG is recommended for use in underground applications. It is recommended for Aluminum to Aluminum and Aluminum to Copper connections where compatibility to rubber products is required. It has the same characteristics as Alnox, but with less electrical efficiency. Stored in a dry environment, Alnox UG has an infinite shelf life. Ordering Information Catalog Number Packaging ALNOXUG10T 8 82 oz tube (250 g), carton of 10 tubes ALNOXUG12CAN One pound can ( 45 kg), carton of 12 cans ALNOXUG1GAL One gallon pail, 10 Lbs (4 5 kg) ALNOXUG5GAL Five gallon pail, 50 Lbs (22 7 kg) Application • Flat to flat connections below 190º C (375º F) such as bus to bus, dead end terminals, aluminum to aluminum and aluminum to copper. • Parallel groove clamps. • Underground applications. Features • Low Electrical Resistance: Alnox UG contains extremely hard metallic particles with sharp, irregular shapes of carefully controlled grain size. This forms many metal to metal contact points for low resistance connections. • Weather Resistant: Alnox UG adheres to pad surfaces and parallel groove clamps, protecting the connection against the environment. • Wide Temperature Tolerance: It is workable at low temperatures , -18º C (0º F) and will not drip below 190º C (375º F).
Please c ontact your AFL Sales Representative for information about our other products or services. FIBER OPTIC CABLE (OPGW, ADSS, Loose Tube) SUBSTATION AND NETWORK UNDERGROUND TRANSMISSION AND DISTRIBUTION FIBER OPTIC CABLE ACCESSORIES
www.AFLglobal.com CAT-03003 11.11.2026
Features:
- MICON connectors
- Crab connectors
- Limiter fuses
Applications:
- Underground electrical distribution
The main emphasis in the development program has been on interchangeability of the connectors and fittings and of their various components. Fortunately, most underground connectors are manufactured to standards established by several public utilities and these standards have gained wide acceptance across the U.S. The advantages of this standardization are great as not only may various components in a system be replaced without concern over the name of the manufacturer, date of manufacture and catalog numbers, but training of personnel and stocking of components are simplified. Compression tools which very often represent a sizeable investment will not be made
obsolete.

C Tapered Compression Sleeve | AFL,CKS Compression Receptacle for MICON Outlets | AFL,LLA 2P1 Limiter Terminal Insulating Sleeve | AFL,CBR Insulated Crab Connector | AFL,LLA 2P2 Limiter Terminal Shell | AFL,LLA 2PL123 Long Limiter Terminal Assembly | AFL,LLA-2PL3 Long Limiter Terminal for Underground Copper Networks | AFL,LLA-2R123 and LLA-2P123 Limiter Terminal Assembly | AFL,LLA-2R3 and LLA-2P3 Limiter Terminal for Underground Networks | AFL,High-Strength MA Cable Receptacle for MICON Outlets | AFL,MICON Coupling MIC Conductor Accessories | AFL,MICON Outlet Plugs P Conductor Accessories | AFL
789